Parameter Value
Description
True
The cyclic restoring after the set time of the parameter
(_:111) Energy
restore interval
will also be synchronized with the system time.
Example:
Energy restore interval
= 30 min; current system time:
12:10 o'clock First restore: 12:30 o'clock; next restore: 13:00 o'clock etc.
Note: When the parameter is activated, the following setting values are possible for the parameter
(_:111)
Energy restore interval
: 1 min; 2 min; 3 min; 4 min; 5 min; 6 min; 10 min; 12 min; 15 min; 20 min;
30 min; 60 min.
Input Signals: >Restoring and >Resetting
Binary Inputs
Description
>Restoring
The restoring of the metered values is initiated via a binary input.
>Reset
The metered value memory is set to 0 through the binary input.
You route these logical signals in the DIGSI routing matrix. Open the function group, for example, Line, where
you created the energy value. There, under the tab Measured values you will find the tab Energy, 3-phase.
In this tab, you will find the logical signals in addition to the measured values.
Measured Values, Energy Values, and Supervision of the Primary System
10.7 Energy Values
SIPROTEC 5, Overcurrent Protection, Manual
1321
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...