EXAMPLE
110-kV overhead line, 150 mm
2
with the data
R´
1
= 0.19 Ω/km
X´
1
= 0.42 Ω/km
You calculate the setting value for the line angle as follows:
[folwibsp-050912-01.tif, 1, en_US]
Parameter: Kr and Kx
•
Default setting
(_:104) Kr
=
1.00
•
Default setting
(_:105) Kx
=
1.00
The
Kr
and
Kx
parameters are used to set the residual compensation factors as scalar values. The
Kr
and
Kx
parameters are relevant for the Fault locator function.
Calculate the setting values for the parameters
Kr
and
Kx
from the line data as follows:
Resistance ratio
Reactance ratio
where:
R
0
Zero-sequence system resistance of the line
X
0
Zero-sequence system reactance of the line
R
1
Positive-sequence system resistance of the line
X
1
Positive-sequence system reactance of the line
This data can either be used for the entire line or as length-related values, since the quotients are length-inde-
pendent. You can calculate the data both from the primary values and from the secondary values.
EXAMPLE
110-kV overhead line, 150 mm
2
with the data:
R
1
/s
0.19 Ω/km positive-sequence system resistance
X
1
/s
0.42 Ω/km positive-sequence system reactance
R
0
/s
0.53 Ω/km zero-sequence system resistance
X
0
/s
1.19 Ω/km zero-sequence system reactance
s
Line length
You receive the following setting values for the parameters
Kr
and
Kx
:
[forerlx1-050912-01.tif, 1, en_US]
Protection and Automation Functions
6.46 Fault Locator
SIPROTEC 5, Overcurrent Protection, Manual
937
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...