Information Target
Processing of Signal Status Changes
Communication interface
IEC 61850-8-1 Client/Server
IEC 60870-5-103/104
DNP V3.0
Special buffering mechanism
Protection interface
PDI
Pass through
IEC 61850-8-1 GOOSE
Pass through
CFC
Pass through
LEDs
Pass through
Binary output
Pass through
Fault recorder
Pass through
Automatic reclosing function
Discard
Circuit-breaker failure protection
Discard
Group indications
Discard
Application and Setting Notes
No Start of the Automatic Reclosing Function
Automatic reclosing is not an effective measure against intermittent ground faults as the protection function
only operates after repeated detection of a fault or after the integration value reaches the predefined
Sum of
extended PU times
. Besides this, its basic design is to prevent thermal overload. For these reasons, the
intermittent ground-fault protection function is not intended to start the automatic reclosing function.
Rooting of Pickup Signals
The signal
Pickup
is supposed to be routed to LED and relay. The signal
Limited pickup (log)
is only
reported to the fault log and communication interface before the signal
Intermittent gnd.flt.
is issued.
This scheme prevents a burst of messages.
i
i
NOTE
To avoid a burst of messages, do not route the signal
Pickup
to the operational log and fault log.
Parameter:
Threshold
•
Default setting
(_:11341:3) Threshold
=
1.00 A
With the
Threshold
parameter, you set the threshold value of the ground current 3I0, measured as RMS
value.
A rather sensitive setting is possible to respond also to short ground faults since the pickup time shortens as
the ground-fault current increases.
Parameter:
No. pickups till interm.GF
•
Default setting
(_:11341:101) No. pickups till interm.GF
=
3
With the parameter
No. pickups till interm.GF
, you set the number of counted
Pickup
signals after
which the ground fault is considered as intermittent.
Parameter:
Pickup extension time
•
Default setting
(_:11341:102) Pickup extension time
=
0.10 s
You can get a stabilized pickup signal with the
Pickup extension time
parameter. This stabilization is
especially important for the coordination with existing static or electromechanical overcurrent protections.
6.13.4
Protection and Automation Functions
6.13 Non-Directional Intermittent Ground-Fault Protection
548
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...