Parameter:
Down integration time
•
Default setting
(_:13861:102) Down integration time
=
3.00 min
Use the parameter
Down integration time
in order to determine the duration until the internal integra-
tion value is linearly reduced from 100 % to 0 %.
For example, if the integration value is 52 %, a duration of 52 % × down integration time is required until the
integration value 0 % is reached. When using this parameter, the preloading of a capacitor can be considered
and therefore released quicker.
If you are knowledgeable about recovery time of stressed capacitors, they can be considered with this param-
eter.
Parameter:
Dropout delay
•
Default setting
(_:13861:7) Dropout delay
=
1.00 s
The parameter
Dropout delay
can be used to prevent resetting of the integral value in the event that the
measured value briefly falls below the dropout threshold.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:2311:101
General:Capacitor rated
current
1.0 A to 100000.0 A
1000.0 A
Inverse-T 1
_:13861:1
Inverse-T 1:Mode
•
off
•
on
•
test
off
_:13861:2
Inverse-T 1:Operate &
flt.rec. blocked
•
no
•
yes
no
_:13861:103
Inverse-T 1:Dropout prin-
ciple
•
with dropout delay
•
with down integration
with down inte-
gration
_:13861:3
Inverse-T 1:Threshold
0.80 p.u. to 3.00 p.u.
1.10 p.u.
_:13861:102
Inverse-T 1:Down inte-
gration time
1 min to 1500 min
3 min
_:13861:7
Inverse-T 1:Dropout
delay
0.00 s to 3600.00 s
1.00 s
Information List
No.
Information
Data Class
(Type)
Type
General
_:2311:301
General:VpeakA
MV
O
_:2311:302
General:VpeakB
MV
O
_:2311:303
General:VpeakC
MV
O
Group indicat.
_:4501:55
Group indicat.:Pickup
ACD
O
_:4501:57
Group indicat.:Operate
ACT
O
Inverse-T 1
_:13861:81
Inverse-T 1:>Block stage
SPS
I
_:13861:54
Inverse-T 1:Inactive
SPS
O
_:13861:52
Inverse-T 1:Behavior
ENS
O
_:13861:53
Inverse-T 1:Health
ENS
O
7.6.3.3
7.6.3.4
Capacitor Bank Protection
7.6 Peak Overvoltage Protection for Capacitors
SIPROTEC 5, Overcurrent Protection, Manual
1025
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...