Parameter Value
Description
RMS value
Select this method of measurement if you want the stage to take harmonics
into account (for example, at capacitor banks). Do not set the
threshold
value
of the tripping stage under 10 V for this method of measurement.
fund. comp. long filter
To implement particularly strong damping of harmonics and transient
disturbances, select this method of measurement. At 2 periods, the length
of the filter is longer than that of the standard filter.
Please note that in this case the pickup time of the stage increases slightly
(see Technical Data).
Parameter: Pickup delay
•
Recommended setting value
(_:331:107) Pickup delay
=
0.00 ms
The
Pickup delay
parameter allows you to delay the analysis of the measurand (to generate the pickup)
depending on the occurrence of the residual voltage. A pickup delay can be necessary if high transients are
anticipated after fault inception due to high line and ground capacitances.
Siemens recommends using the default setting
Pickup delay
=
0.00 ms
.
Parameter: Threshold
•
Default setting
(_:331:3) Threshold
=
30.000 V
27
The threshold value of the function is set as the zero-sequence voltage V
0
. The device calculates the zero-
sequence voltage V
0
either from the residual voltage measured via the broken-delta winding or from the
3 phase-to-ground voltages.
The setting value depends on the system grounding:
•
Since virtually the full residual voltage occurs during ground faults in isolated or arc-suppression-coil-
grounded systems, the setting value is uncritical there. It should range between 20 V and 40 V. A higher
sensitivity (= lower threshold value) can be necessary for high fault resistances.
•
You should select a more sensitive (smaller) value in a grounded system. This value must be higher than
the maximum residual voltage anticipated during operation caused by system unbalances.
EXAMPLE
For an isolated system
The residual voltage is measured via the broken-delta winding:
•
If the ground fault is fully unbalanced, a residual voltage of 100 V is present at the device terminals.
•
The threshold value should be set so that the stage picks up on 50 % of the full residual voltage.
•
At full residual voltage, the zero-sequence voltage is 100 V/√3 = 57.7 V
Setting value: 0.5 ⋅ 57.7 V = 28.9 V ≈ 30 V
Parameter: Dropout ratio
•
Recommended setting value
(_:331:4) Dropout ratio
=
0.95
The recommended set value of
0.95
is appropriate for most applications. The dropout ratio can be reduced
for example, to 0.98 to achieve a high measurement precision.
Parameter: Operate delay
•
Default setting
(_:331:6) Operate delay
=
3.00 s
The
Operate delay
allows you to prevent transient residual voltages from initiating a trip. The setting
depends on the specific application.
27
The specific setting limits depend on the transformer data and transformer connections set.
Protection and Automation Functions
6.24 Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage
SIPROTEC 5, Overcurrent Protection, Manual
707
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...