Settings
Addr.
Parameter
C
Setting Options
Default Setting
Pulse detect.#
_:1
Pulse detect.#:Mode
•
off
•
on
•
test
off
_:2
Pulse detect.#:Operate &
flt.rec. blocked
•
no
•
yes
no
_:102
Pulse detect.#:V0>
threshold value
0.300 V to 200.000 V
30.000 V
_:101
Pulse detect.#:3I0>
threshold value
1 A @ 100 Irated 0.030 A to 35.000 A
0.200 A
5 A @ 100 Irated 0.15 A to 175.00 A
1.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
0.200 A
5 A @ 50 Irated
0.15 A to 175.00 A
1.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
0.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
1.000 A
_:103
Pulse detect.#:3I0 delta
pulse off-on
5 % to 50 %
10 %
_:104
Pulse detect.#:Pulse-on
duration
0.20 s to 10.00 s
1.00 s
_:105
Pulse detect.#:Pulse-off
duration
0.20 s to 10.00 s
1.50 s
_:109
Pulse
detect.#:Max.tolera.puls
e-on or off
0.02 s to 2.00 s
0.15 s
_:107
Pulse detect.#:No. of
pulses for operate
2 to 100
3
_:108
Pulse detect.#:Moni-
toring time(in pulses)
2 to 100
5
Information List
No.
Information
Data Class
(Type)
Type
Pulse detect.#
_:81
Pulse detect.#:>Block stage
SPS
I
_:54
Pulse detect.#:Inactive
SPS
O
_:52
Pulse detect.#:Behavior
ENS
O
_:53
Pulse detect.#:Health
ENS
O
_:302
Pulse detect.#:Detected pulses
MV
O
_:55
Pulse detect.#:Pickup
ACD
O
_:56
Pulse detect.#:Operate delay expired
ACT
O
_:57
Pulse detect.#:Operate
ACT
O
6.15.13.3
6.15.13.4
Protection and Automation Functions
6.15 Sensitive Ground-Fault Detection
SIPROTEC 5, Overcurrent Protection, Manual
627
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...