Addr.
Parameter
C
Setting Options
Default Setting
_:781:107
Inverse-T 1:Time dial
0.00 to 15.00
1.00
Information List
No.
Information
Data Class
(Type)
Type
Group indicat.
_:4501:55
Group indicat.:Pickup
ACD
O
_:4501:57
Group indicat.:Operate
ACT
O
Inverse-T 1
_:781:81
Inverse-T 1:>Block stage
SPS
I
_:781:500
Inverse-T 1:>Block delay & op.
SPS
I
_:781:54
Inverse-T 1:Inactive
SPS
O
_:781:52
Inverse-T 1:Behavior
ENS
O
_:781:53
Inverse-T 1:Health
ENS
O
_:781:60
Inverse-T 1:Inrush blocks operate
ACT
O
_:781:59
Inverse-T 1:Disk emulation running
SPS
O
_:781:55
Inverse-T 1:Pickup
ACD
O
_:781:56
Inverse-T 1:Operate delay expired
ACT
O
_:781:57
Inverse-T 1:Operate
ACT
O
Stage with User-Defined Characteristic Curve
Description
This stage is only available in the advanced function type.
This stage is structured the same way as the Inverse-time overcurrent protection – advanced stage (see
chapter
). The only differences are as follows:
•
You can define the characteristic curve as desired.
•
The pickup and dropout behaviors of this stage are determined by the standard parameter
Threshold
and, if necessary, by an additional parameter
Threshold (absolute)
.
User-Defined Characteristic Curve
With the user-defined characteristic curve, you can define the operate curve point by point using up to 30
value pairs of current and time. The device uses linear interpolation to calculate the characteristic curve from
these values. You can also define a dropout characteristic curve if you wish.
Pickup and Dropout Behaviors with the User-Defined Characteristic Curve
When the input variable exceeds the
Threshold
value by 1.1 times, the characteristic curve is processed. An
integrating method of measurement totalizes the weighted time. The weighted time results from the charac-
teristic curve. For this, the time that is associated with the present current value is determined from the char-
acteristic curve. Once the weighted time exceeds the value 1, the stage operates.
When the measured value falls short of the pickup value by a factor of 1.045 (0.95 x 1.1 x
Threshold
value),
the dropout is started. The pickup will be indicated as clearing. You can influence the dropout behavior via
setting parameters. You can select between instantaneous dropout (totalized time is deleted) or dropout
according to the characteristic curve (reduction of totalized time depending on the characteristic curve). The
dropout according to characteristic curve (disk emulation) is the same as turning back a rotor disk. The
weighted reduction of the time is initiated from 0.9 of the set threshold value.
6.5.5.4
6.5.6
6.5.6.1
Protection and Automation Functions
6.5 Overcurrent Protection, Ground
SIPROTEC 5, Overcurrent Protection, Manual
397
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...