Information List
No.
Information
Data Class
(Type)
Type
User curve #
_:81
User curve #:>Block stage
SPS
I
_:501
User curve #:>Release delay & op.
SPS
I
_:84
User curve #:>Activ. dyn. settings
SPS
I
_:500
User curve #:>Block delay & op.
SPS
I
_:54
User curve #:Inactive
SPS
O
_:52
User curve #:Behavior
ENS
O
_:53
User curve #:Health
ENS
O
_:60
User curve #:Inrush blocks operate
ACT
O
_:62
User curve #:Dyn.set. AR cycle1act.
SPS
O
_:63
User curve #:Dyn.set. AR cycle2act.
SPS
O
_:64
User curve #:Dyn.set. AR cycle3act.
SPS
O
_:65
User curve #:Dyn.set. ARcycl.>3act
SPS
O
_:66
User curve #:Dyn.set. CLP active
SPS
O
_:67
User curve #:Dyn.set. BI active
SPS
O
_:68
User curve #:Dyn. set. blks. pickup
SPS
O
_:59
User curve #:Disk emulation running
SPS
O
_:55
User curve #:Pickup
ACD
O
_:309
User curve #:Direction
ACD
O
_:56
User curve #:Operate delay expired
ACT
O
_:57
User curve #:Operate
ACT
O
Direction Determination
Description
General
Every phase has a separate direction-measuring element. If the threshold value in a phase is exceeded, the
direction determination is started for this phase. If there are multiphase short circuits, all measuring elements
involved perform direction determination independently. If one of the determined directions matches the set
direction, the stage picks up (see descriptions of the stage logic).
The direction is determined by calculating the phase angle between the short-circuit current and a reference
voltage.
Measurands for Direction Determining
The directional measuring element uses the short-circuit current of the phase concerned and the cross-polar-
ized phase-to-phase voltage (as the reference voltage) to determine the direction. This means that the direc-
tion can still be determined unambiguously and correctly, even if the short-circuit voltages collapse
completely when a 1-phase or 2-phase fault occurs (close-up fault).
The phase-to-phase voltages are calculated when phase-to-ground voltages are connected.
The cross-polarized voltage (reference voltage) is vertical in relation to the short-circuit voltages for 1-phase-
to-ground faults (
, left). For 2-phase short circuits, the position of the reference voltages changes
up to 30
o
, depending on the extent to which the short-circuit voltages collapse (
6.6.6.4
6.6.7
6.6.7.1
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases
SIPROTEC 5, Overcurrent Protection, Manual
433
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...