Figure 6-122
Logic Diagram of the Cross-Stage Functionality of the Non-Directional Function
Operational Measured Value φ(I,V)
The function block calculates the angle between IN and V0 and makes the angle available as function meas-
ured value
Phi(I,V)
.
[DwPhINU0, 1, en_US]
Figure 6-123
Sign Definition for the Measured Value
Fault-Extinction Detection
The extinction of the fault is characterized by the fact that the zero-sequence voltage subsides. Depending on
the system conditions and fault characteristics, this process can last several 100 ms. If a continuously falling
zero-sequence voltage is detected during the set time
Decay time V0
, then the fault is considered extin-
guished. The signal
Flt. extinction det.
is issued.
Thus, the possibility exists, for example, to block the 3I0> stage with cos φ or sin φ measurement directly
after the fault extinction, in order to avoid an overfunction during the subsiding process with a very sensitive
setting of the stage.
Angle-Error Compensation
The high reactive power factor in the arc-suppression-coil-ground system and the unavoidable air-gap of the
core balance current transformer often make necessary a compensation of the angle error of the core balance
current transformer. Using the characteristic shown in the following figure, the device approaches the angle
error of the core balance current transformer with sufficient precision.
Protection and Automation Functions
6.15 Sensitive Ground-Fault Detection
SIPROTEC 5, Overcurrent Protection, Manual
565
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...