Parameter: Release threshold
•
Recommended setting value
(_:101) Release threshold
=
0.5 A
for I
rated
= 1 A or
2.5
A
for I
rated
= 5 A
The
Release threshold
parameter is used to set the lower limit of the maximum phase current (I
max
).
Parameter: Operate delay
•
Recommended setting value
(_:6) Operate delay
=
5.00 s
Set the
Operate delay
parameter so that overfunctions due to disturbing influences (such as switching
operations) are avoided.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Supv. balan. I
_:1
Supv. balan. I:Mode
•
off
•
on
•
test
off
_:101
Supv. balan. I:Release
threshold
1 A @ 100 Irated 0.030 A to 35.000 A
0.500 A
5 A @ 100 Irated 0.15 A to 175.00 A
2.50 A
1 A @ 50 Irated
0.030 A to 35.000 A
0.500 A
5 A @ 50 Irated
0.15 A to 175.00 A
2.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
0.500 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
2.500 A
_:102
Supv. balan. I:Threshold
min/max
0.10 to 0.95
0.50
_:6
Supv. balan. I:Delay
supervision alarm
0.00 s to 100.00 s
5.00 s
Information List
No.
Information
Data Class
(Type)
Type
Supv. balan. I
_:82
Supv. balan. I:>Block function
SPS
I
_:54
Supv. balan. I:Inactive
SPS
O
_:52
Supv. balan. I:Behavior
ENS
O
_:53
Supv. balan. I:Health
ENS
O
_:71
Supv. balan. I:Failure
SPS
O
Current-Sum Supervision
Overview of Functions
In healthy system operation, the sum of all currents at one measuring point must be approximately 0. The
Current-sum supervision function monitors the sum of all currents of one measuring point in the secondary
circuit. It detects connection errors during commissioning or short circuits and interruptions in the secondary
circuit.
For summation of the currents, the device requires the phase currents and the ground current of the current
transformer neutral point or of a separate ground-current transformer at this measuring point. Select the
following connection variant:
•
Current-transformer connections connected to 3 current transformers and the neutral point (see
in the Attachment)
9.3.10.5
9.3.10.6
9.3.11
9.3.11.1
Supervision Functions
9.3 Supervision of the Secondary System
SIPROTEC 5, Overcurrent Protection, Manual
1275
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...