Table 3-14
Available Bits - Minimum Constellation Baud Rate 512/2048 kbit/s
Priority 1
Priority 2
Priority 3
Type 1
48 bits
128 bits
384 bits
Type 2
96 bits
200 bits
1024 bits
Table 3-15
Requirement in Bits
Signal Type
Size in Bits
SP (single-point indication)
1 bit
DP (double-point indication)
2 bits
IN (metered values)
32 bits
MW (measured values)
8
32 bits
ACT
4 bits
Table 3-16
Possible Dropout Values
Signal Type
Dropout Values
SP (single-point indication)
Outgoing, Incoming, Hold
DP (double-point indication)
On, Off, Intermediate Position, Disturbed Position,
Hold
IN (metered values)
0, Hold
MW (measured values)
0, Hold
ACT
Hold
i
i
NOTE
If the protection link fails, these values can be set on the receiver side.
EXAMPLE
2 devices are connected via a 64-kbits channel. This is a type 1 topology. 8 bits are freely available for priority
1. Now, for example, 4 SPS and 2 DPS can be routed:
4 x 1 bit + 2 x 2 bits = 8 bits
i
i
NOTE
Measured values are transmitted as primary values.
EXAMPLE
For the rated current display in the receiving device
When I
rated
= 1000 A in the transmitting device and I
Load
= 200 A, the number 200 is displayed in the receiving
device.
Remote Data Transmission: Routing of the Indications and Measured Values to the Protection Interface
The transmission is organized in the form of a data bar which is continuously exchanged between the devices.
For this, see
.
A device indication or measured value is allocated to a definite data area of the bar.
8
The complex phasors of a measuring point are pre-routed
System Functions
3.5 Protection Communication
130
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...