Function Supervision for Automatic Operation
If the actual voltage exceeds or falls below the set bandwidth for longer than the set time delay, this situation
is shown by the indication
(_:14011:309) Auto Monitor
. If the actual voltage returns to the voltage
range, the indication is reset. You can switch off the function monitor with a time delay = 0 min.
[lofktueb-090913-01.vsd, 1, en_US]
Figure 8-108
Logic of the Function Supervision for Automatic Operation
Line Compensation
When using line compensation, the voltage drop of a phase that is connected to a transformer can be
included. In this case, 2 processes are available:
•
Z compensation (LDC-Z)
•
X and R compensation (LDC-XandR)
i
i
NOTE
Line compensation is only active if power is flowing in the direction of the line.
Z Compensation (LDC-Z)
Z compensation allows you to include the voltage drop of a line connected to the transformer. You can switch
Z compensation on or off. If cos φ is roughly constant, you can use Z compensation. Setting the parameters
requires the calculation of the voltage increase (
Target voltage rising
) taking into consideration the
load current (
Max load current
).
The parameter
Target voltage rising
represents the voltage drop across the line as a % under rated
load.
You can find more information and the calculation in chapter
8.9.4 Application and Setting Notes Voltage
.
In case of active Z compensation, you must limit the maximum permitted voltage increase in relation to the
target voltage to avoid too high voltage at the transformer. To do this, set the parameter
Max load
current
. In addition, the parameter
Vmax threshold
is active. If the actual voltage exceeds this threshold
value, no more higher adjusting commands are issued.
Control Functions
8.9 Voltage Controller
1206
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...