Figure 6-34
Logic Diagram of Measured-Value Selection
Both options are only available for the current-transformer connection types
3-phase + IN
and
3-phase +
IN-separate
. For other connection types respectively, only one option is possible. If you select an option
that is not allowed, an inconsistency message is given.
Depending on the CT secondary rated current, the CT connection type, and the selected setting, the secondary
threshold setting range varies according to the following table.
Table 6-2
Threshold Setting Range
Connec-
tion
Type
Measured
Value
CT
Terminal
Type
Threshold Setting
Range (rated I-sec.:
ph = 1 A, IN = 1 A)
Threshold Setting
Range (rated I-sec.:
ph = 1 A, IN = 5 A)
Threshold Setting
Range (rated I-sec.:
ph = 5 A, IN = 1 A)
Threshold Setting
Range (rated I-sec.:
ph = 5 A, IN = 5 A)
3ph + IN
3I0 calcu-
lated
4 * Protec-
tion
0.010 A to 35.000 A N/A
N/A
0.050 A to 175.00 A
4 * Meas-
urement
0.001 A to 1.600 A
N/A
N/A
0.002 A to 8.000 A
IN meas-
ured
4 * Protec-
tion
0.010 A to 35.000 A N/A
N/A
0.050 A to 175.00 A
4 * Meas-
urement
0.001 A to 1.600 A
N/A
N/A
0.002 A to 8.000 A
3ph + IN-separate
3I0 calcu-
lated
4 * Protec-
tion
0.010 A to 35.000 A 0.010 A to 35.000 A 0.050 A to 175.00 A 0.050 A to 175.00 A
3 * Protec-
tion, 1 *
sen.
0.010 A to 35.000 A 0.010 A to 35.000 A 0.050 A to 175.00 A 0.050 A to 175.00 A
4 * Meas-
urement
0.001 A to 1.600 A
0.001 A to 1.600 A
0.002 A to 8.000 A
0.002 A to 8.000 A
IN meas-
ured
4 * Protec-
tion
0.010 A to 35.000 A 0.050 A to 175.00 A 0.010 A to 35.000 A 0.050 A to 175.00 A
3 * Protec-
tion, 1 *
sen.
0.001 A to 1.600 A
0.002 A to 8.000 A
0.001 A to 1.600 A
0.002 A to 8.000 A
4 * Meas-
urement
0.001 A to 1.600 A
0.002 A to 8.000 A
0.001 A to 1.600 A
0.002 A to 8.000 A
Application and Setting Notes
Parameter:
Measured value
•
Recommended setting value
Measured value
=
IN Measured
This parameter is not available in the basic function.
Parameter Value
Description
6.5.3.2
Protection and Automation Functions
6.5 Overcurrent Protection, Ground
380
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...