Undervoltage-Controlled Reactive-Power Protection
Setting Values
Threshold value
Power Q
1.00 % to 200.00 %
Increments of 0.01 %
Voltage of protection
stage
3.000 to 175.000
Increments of 0.001 V
Voltage of reclosure
stage
3.000 V to 340.000 V
Increments of 0.001 V
Current I
1
release threshold
1 A @ 50 and 100 Irated 0.030 A to 10.000 A
Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 50.00 A
Increments of 0.01 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
Increments of 0.001 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
Increments of 0.001 A
Operate delay
0.00 s to 60.00 s
Increments of 0.01 s
Release time delay of reclosure stage
0.00 s to 3600.00 s
Increments of 0.01 s
Dropout Ratio
Protection stage
Reactive-power flow Q
Approx. 0.95
Voltage
Approx. 1.02
Release current
Approx. 0.95
Reclosure stage
Voltage
Approx. 0.98
Release current
Approx. 0.95
Times
Pickup time
Approx. 55 ms + OOT
140
at 50 Hz
Approx. 45 ms + OOT at 60 Hz
Dropout time
Approx. 55 ms + OOT at 50 Hz
Approx. 45 ms + OOT at 60 Hz
Tolerances
Current I
1
1 % of the setting value or 5 mA (I
rated
= 1 A)
or 25 mA (I
rated
= 5 A)
Voltage
0.5 % of the setting value or 0.05 V
Power Q
0.5 % S
rated
± 3 % of the setting value
(S
rated
: rated apparent power)
Time delays
1 % of the setting value or 10 ms
Reclosure time delay
1 % of the setting value or 10 ms
Frequency Operating Range
0.9 ≤ f/f
rated
≤ 1.1
According to specified tolerances
10 Hz ≤ f < 0.9 f
rated
1.1 f
rated
< f ≤ 80 Hz
Slightly expanded tolerances
12.47
140
OOT (Output Operating Time): additional delay of the output medium used, for example 5 ms with fast relays
Technical Data
12.47 Undervoltage-Controlled Reactive-Power Protection
1534
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...