Parameter Value
Description
yes
Harmonic analysis process activated.
no
Harmonic analysis process deactivated.
i
i
NOTE
Make sure that at least one process is activated. Siemens recommends retaining the advised setting values.
Parameter: 2nd harmonic content
•
Recommended setting value
(_:102) 2nd harmonic content
=
15 %
With the parameter
2nd harmonic content
, you can specify the pickup value of the harmonic anal-
ysis function. The setting value of 15 % is practicable for most transformers.
Parameter: Crossblocking
•
Recommended setting value
(_:112) Crossblocking
=
no
Parameter Value
Description
no
Through the CWA process working in parallel in the inrush-current detec-
tion, the function is not activated as standard.
yes
If a subfunction of the inrush-current detection is identified in the course of
the closure trials during commissioning, set the parameter
Cross-
blocking
to
yes
.
Parameter: Crossblocking time
•
Default setting
(_:109) Crossblocking time
=
0.06 s
You define the duration of this blocking with the
Crossblocking time
parameter. The default setting
of
0.06 s
(about 3 periods) has proven practicable. Set the time as short as possible and check the value
during the closure trials. The parameter
Crossblocking time
is inactive at
Crossblocking
=
no
.
Parameter: Start flt.rec
•
Default setting
(_:114) Start flt.rec
=
yes
With the
Start flt.rec
parameter, you determine whether a fault record should be started upon
pickup of the inrush-current detection. The following settings are possible:
Parameter Value
Description
no
No fault recording starts with pickup.
yes
The fault recording starts with pickup. When the protection function is
blocked by the inrush-current detection, a fault recording is started never-
theless.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Inrush detect.
_:1
Inrush detect.:Mode
•
off
•
on
•
test
on
6.8.5
Protection and Automation Functions
6.8 Inrush-Current Detection
SIPROTEC 5, Overcurrent Protection, Manual
491
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...