Parameter Value
Description
disk emulation
Select this setting if the device is coordinated with electromechanical
devices or other devices which perform a dropout after a disk emulation.
instantaneous
Select this setting if the dropout is not to be performed after disk emulation
and an instantaneous dropout is desired instead.
Parameter:
1-pole operate allowed
•
Default setting
(_:691:11) 1-pole operate allowed
=
no
The parameter must be set for the specific application.
Parameter Value
Description
no
The stage always operates 3-pole.
yes
The stage operates phase-selectively. However, tripping by the device
(generated in the trip logic of the Circuit-breaker function group) is always
3-pole because the device does not support phase-selective tripping.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:691:1
Inverse-T 1:Mode
•
off
•
on
•
test
off
_:691:2
Inverse-T 1:Operate &
flt.rec. blocked
•
no
•
yes
no
_:691:11
Inverse-T 1:1-pole
operate allowed
•
no
•
yes
no
_:691:26
Inverse-T 1:Dynamic
settings
•
no
•
yes
no
_:691:27
Inverse-T 1:Blk. w. inrush
curr. detect.
•
no
•
yes
no
_:691:8
Inverse-T 1:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:691:120
Inverse-T 1:I0 elimina-
tion
•
no
•
yes
no
_:691:3
Inverse-T 1:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A
7.50 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.500 A
5 A @ 50 Irated
0.15 A to 175.00 A
7.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.500 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
7.500 A
_:691:108
Inverse-T 1:Pickup delay
0.00 s to 60.00 s
0.00 s
_:691:130
Inverse-T 1:Type of char-
acter. curve
_:691:113
Inverse-T 1:Min. time of
the curve
0.00 s to 1.00 s
0.00 s
_:691:131
Inverse-T 1:Reset
•
instantaneous
•
disk emulation
disk emulation
_:691:101
Inverse-T 1:Time dial
0.00 to 15.00
1.00
_:691:115
Inverse-T 1:Additional
time delay
0.00 s to 60.00 s
0.00 s
6.3.5.3
Protection and Automation Functions
6.3 Overcurrent Protection, Phases
346
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...