Figure 6-124
Correction of the Transmission Characteristic Curve of a Core Balance Current Transformer
Ground-Fault Indication, Stabilization at Intermittent Ground Fault
The indication
Ground fault
indicates the ground fault and manages the ground-fault log (see
). The corresponding information of the stages used is accessed for the generation of
this indication.
The indication
Ground fault
contains the direction information, independent of the parameterized
working direction of a stage. The indication is thus suited for transfer to a station.
To avoid a flood of indications in case of an intermittent ground fault, a maximum of 30 status changes of this
indication is logged per ground fault. An intermittent ground fault must be treated as a ground fault so that
the stabilization can take action. This is ensured with the parameter
Dropout delay
, by the dropout of the
indication
Ground fault
being delayed. If the next ignition of the ground fault takes place during the
dropout delay, the indication does not drop out and the log remains open.
i
i
NOTE
The
Ground fault
indication in the general stage must be routed to the ground-fault log. If not, you can
meet an overflow of the ground-fault log when an intermittent ground fault occurs.
Ground-Fault Log
Ground faults can be recorded in a designated buffer, the ground-fault log. As long as the
Operate &
flt.rec. blocked
parameter is set to
yes
, all indications routed into the ground-fault log are written in
the ground-fault log.
The criterion for opening the ground-fault log is the raising of any indication which is routed to the ground-
fault log, for example, the indication
Ground fault
. The criterion for closing is the clearing of all routed
indications.
Related Topics
You can find general notes on the ground-fault login chapter Indications under
Value Indications
If the following value indications can be calculated, they are written into the log (ground-fault log or fault log)
at the time of the 1st raising ground-fault indication and the 1st operate indication of any stage.
•
3I0 (value)
•
3I0 active component
•
3I0 reactive component
Protection and Automation Functions
6.15 Sensitive Ground-Fault Detection
566
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...