Measurement of the fundamental comp.:
This measurement method processes the sampled current values and numerically filters out the funda-
mental component.
•
Measurement of the parameter value RMS value:
This measurement method determines the current amplitude from the sampled values according to the
definition equation of the RMS value. Harmonics are included in the analysis.
Pickup Mode
The
Pickup mode
parameter defines whether the protection stage picks up if all 3 measuring elements
detect the undercurrent condition (
3 out of 3
) or if only 1 measuring element has to detect the undercur-
rent condition (
1 out of 3
).
Blocking the Stage
When blocked, the picked-up protection stage will drop out. Blocking the stage is possible externally or inter-
nally via the binary input signal
>Block stage
.
Activation and Blocking of the Stage Depending On the Circuit-Breaker Condition
With the parameter
Activation
, you define if the Undercurrent protection stage is always active or only
active if the circuit breaker is indicating closed.
If the parameter
Activation
is set to
with CB closed
and the local circuit breaker is not closed, the func-
tion Undercurrent protection is blocked and no pickup is generated.
The circuit-breaker position is detected as closed if one of the following conditions is met:
•
The binary inputs are connected to the auxiliary contacts of the circuit breaker. The circuit-breaker switch
position is detected as closed via the related binary inputs of the Position indication. This is also true
under the condition that no phase current is flowing.
•
The current-flow criterion indicates that the circuit breaker is closed. This is also true under the condition
that the auxiliary contacts indicate the circuit breaker as open.
Application and Setting Notes
Parameter:
Activation
•
Default setting
(_:13051:103) Activation
=
with CB closed
Parameter Value
Description
with CB closed
The Undercurrent protection is active only when the circuit-breaker posi-
tion is detected as closed.
A precondition is, that the Position indication is routed to binary inputs to
obtain the CB position information via the CB auxiliary contacts. If this is not
the case, the function will always be inactive.
always active
The Undercurrent protection stage is always active independent of the
position of the circuit breaker.
Parameter:
Method of measurement
•
Recommended setting value
(_:13051:8) Method of measurement
=
fundamental comp.
With the
Method of measurement
parameter, you define whether the stage uses the
fundamental
comp.
(standard method) or the calculated
RMS value
.
Parameter Value
Description
fundamental comp.
Select this method of measurement if harmonics or transient current peaks
are to be suppressed.
Siemens recommends using this method as the standard method.
6.16.4
Protection and Automation Functions
6.16 Undercurrent Protection
630
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...