Phase-angle rota-
tion
0°
30°
60°
90°
120° 150° 180° 210° 240° 270° 300° 330°
Vector group
numeral
0
1
2
3
4
5
6
7
8
9
10
11
In the function group, the following information is displayed additionally in the setting sheet:
•
Side number
•
Identification of the measuring points used
•
Adaptation factor for the 3-phase measuring point (with reference to the side)
Each
Vector group numeral
can be set from 0 to 11 to the extent possible. Thus, for example, only even
numbers are possible for the vector group Yy and Dd and only odd numbers are possible for Yd and Dy.
Parameter:
Side number
•
Default setting
(_:1781:14611:130) Side number
=
not assigned
The
Side number
parameter shows you which capacitor bank side is currently valid for the following param-
eters. The side number (
Side 1
to
Side 3
) is automatically assigned with the connection to a capacitor bank
side.
Parameter:
MI3ph1 usesMeasP with ID
•
Default setting
(_:1781:14611:210) MI3ph1 usesMeasP with ID
=
0
The
MI3ph1 usesMeasP with ID
parameter shows you which 3-phase measuring point is connected to
the capacitor bank side. Every measuring point is assigned a unique ID.
Parameter:
MI3ph2 usesMeasP with ID
•
Default setting
(_:1781:14611:211) MI3ph2 usesMeasP with ID
=
0
The
MI3ph2 usesMeasP with ID
parameter shows you which 3-phase measuring point is connected to
the capacitor bank side. Every measuring point is assigned a unique ID.
Parameter:
CT mismatch M I-3ph 1
•
Default setting
(_:1781:14611:215) CT mismatch M I-3ph 1
=
0.000
The
CT mismatch M I-3ph 1
parameter shows you the magnitude adaptation of the phase currents of the
1st assigned measuring point. The numerical value results from the ratio of the primary rated current of the
current transformer to the rated current of the side.
Parameter:
CT mismatch M I-3ph 2
•
Default setting
(_:1781:14611:217) CT mismatch M I-3ph 2
=
0.000
The
CT mismatch M I-3ph 2
parameter shows you the magnitude adaptation of the phase currents of the
2nd assigned measuring point.
Write-Protected Settings
The settings listed here are used primarily for understanding during configuration of the function groups. They
are calculated on the basis of other settings and cannot be directly changed.
Addr.
Parameter
C
Range of Values
Default Setting
Rated values
_:1781:15571:103
Rated apparent power
0.20 MVA to 5000.00 MVA
692.82 MVA
5.5.3.4
Function-Group Types
5.5 Function-Group Type Capacitor Bank Differential Protection
SIPROTEC 5, Overcurrent Protection, Manual
235
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...