The compensation eliminates the operational differential voltage by adjusting the voltage matching factors.
The adjusted phasors of the matching factor are calculated at the compensation moment, with the following
formula (for phase A):
•
Grounded capacitor-bank system
k
cp,A
= V
BB,A
/ V
tap,A
•
Isolated capacitor-bank system
k
cp,A
= (V
BB,A
- V
N
) / (V
tap,A
- V
N
)
With
V
BB,A
Busbar voltage, phase A
V
tap,A
Tap voltage, phase A
k
cp,A
Calculated matching factor at the compensation moment, phase A
V
N
Neutral-point-to-ground voltage
The calculation also applies to the calculation of the voltage matching factors of phase B and phase C.
The phasors of the calculated voltage matching factors k
cp
are stored and used for calculation of the differen-
tial voltage until the next compensation is applied or until the compensation is reset.
The phasors of the calculated voltage matching factors k
cp
are displayed as functional measured values after
the compensation is applied. In addition, the compensated differential voltage
Vdiff.cp
is available as func-
tional measured value.
Vdiff.cp
is the differential voltage at the moment of the compensation compared to
the not compensated status. The compensated differential voltage
Vdiff.cp
is calculated with the following
formula (for phase A):
•
Grounded capacitor-bank system
V
diff.cp,A
= | (V
BB,A
- V
N
) - k
cp,A
⋅ (V
tap,A
- V
N
)|
•
Isolated capacitor-bank system
V
diff.cp,A
= | V
BB,A
- k
cp,A
⋅ V
tap,A
|
With
k
cp,A
Calculated matching factor at the compensation moment, phase A
V
BB,A
Voltage from the busbar, phase A
V
tap,A
Voltage from the tap, phase A
V
N
Neutral-point-to-ground voltage
This calculation also applies to the calculation of the compensated differential voltage of phase B and phase C.
Manual Compensation via Binary Input Signal
Manual compensation via binary input signals is available.
The following indications describe the status of the compensation:
Indication
Description
Alg. not compensated
The algorithm is not compensated. Compensated values are not available.
Compens. succeeded
If the existing unbalance has been compensated manually, this indication is
issued (as transient indication).
By activation of the binary input signal
>Compensate
, the manual compensation is started and the differen-
tial voltage that exists at that moment is compensated to 0. The value of V
diff.
becomes 0.
For the reliability of manual compensation, the binary input signal
>Compensate
has a preset software
filtering time (configurable in DIGIS) of 20 ms.
Capacitor Bank Protection
7.7 Voltage Differential Protection for Capacitors
1036
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...