Properties
Function
To Be Found in
Treatment of spontaneous
position changes
(Gen. Soft-
ware Filt./Spont. Software Filt.)
If you select the
General soft-
ware filter
setting, the general
settings for software filtering of
spontaneous position changes and
for position changes caused by a
switching command apply. By
selecting
Spontaneous soft-
ware filter
, a separate filtering
is activated for spontaneous posi-
tion changes.
Position of the Control function
block
34
Spontaneous software
filtering time
Software filtering time for sponta-
neous position changes
Position of the Control function
block
34
Spontaneous retrigger
filter
(yes/no)
Switching on/off retriggering of the
filtering time by spontaneous posi-
tion change
Position of the Control function
block
34
Spontaneous indication
timestamp before filtering
(yes/no)
Consideration of the hardware
filtering time for position-detection
time stamp in case of a sponta-
neous change
Position of the Control function
block
34
Inhibit intermediate posi-
tion for a spontaneous
chng.
(yes/no)
When activated, only the sponta-
neous change to the intermediate
position is suppressed by the dura-
tion of the software filtering time.
Position of the Control function
block
34
Table 8-3
Setting Options of the Controllable
Position
in the Circuit-Breaker Function Block (Chatter
Blocking)
Properties
Function
To Be Found in
Chatter blocking
(yes/no)
Switching chatter blocking on/off
Position of the Circuit-breaker
function block
34
Table 8-4
Additional Settings in the Device Settings having Effects on the Circuit Breaker
Properties
Function
To Be Found in
Number of permissible
status changes
Chatter-blocking setting value:
Once for the entire device
Device settings (to be found under
Settings)
Chatter test time
Number of chatter tests
Chatter idle time
Chatter check time
The inputs and outputs as well as the setting options of the Circuit-breaker and Control function blocks are
described in the next section (see
8.2.2.3 Connection Variants of the Circuit Breaker
).
Interlocking
The
Interlocking
function block generates the releases for switchgear interlocking protection. The actual
interlocking conditions are deposited in CFC. For more information on this, see the overreaching chapter
8.3.1 Command Checks and Switchgear Interlocking Protection
.
Application and Setting Notes
Circuit Breaker
The Circuit-breaker function block in the SIPROTEC 5 device represents the physical switch device. The task of
the circuit breaker is to replicate the switch position from the status of the binary inputs.
8.2.2.2
Control Functions
8.2 Switching Devices
1080
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...