The setting value for the
Time dial
parameter is derived from the time-grading chart that has been
prepared for the electrical power system.
Where no time grading and therefore no displacement of the characteristic curve is required, leave the param-
eter
Time dial
at 1 (default setting).
Settings
Addr.
Parameter
C
Setting Options
Default Setting
V-dependent 1
_:11491:1
V-dependent 1:Mode
•
off
•
on
•
test
off
_:11491:2
V-dependent 1:Operate
& flt.rec. blocked
•
no
•
yes
no
_:11491:27
V-dependent 1:Blk. w.
inrush curr. detect.
•
no
•
yes
no
_:11491:8
V-dependent 1:Method
of measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:11491:3
V-dependent
1:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A
7.50 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.500 A
5 A @ 50 Irated
0.15 A to 175.00 A
7.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.500 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
7.500 A
_:11491:101
V-dependent 1:Type of
character. curve
_:11491:102
V-dependent 1:Reset
•
instantaneous
•
disk emulation
disk emulation
_:11491:103
V-dependent 1:Time dial
0.05 to 15.00
1.00
Information List
No.
Information
Data Class
(Type)
Type
Group indicat.
_:4501:55
Group indicat.:Pickup
ACD
O
_:4501:57
Group indicat.:Operate
ACT
O
V-dependent 1
_:11491:81
V-dependent 1:>Block stage
SPS
I
_:11491:500
V-dependent 1:>Block delay & op.
SPS
I
_:11491:54
V-dependent 1:Inactive
SPS
O
_:11491:52
V-dependent 1:Behavior
ENS
O
_:11491:53
V-dependent 1:Health
ENS
O
_:11491:60
V-dependent 1:Inrush blocks operate
ACT
O
_:11491:59
V-dependent 1:Disk emulation running
SPS
O
_:11491:55
V-dependent 1:Pickup
ACD
O
_:11491:56
V-dependent 1:Operate delay expired
ACT
O
_:11491:57
V-dependent 1:Operate
ACT
O
6.4.3.3
6.4.3.4
Protection and Automation Functions
6.4 Voltage-Dependent Overcurrent Protection, Phases
SIPROTEC 5, Overcurrent Protection, Manual
365
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...