Signal Name
Description
Type
Op.ct.
The information counts the number of disconnector
switching cycles.
INS
Control
It is the task of the controls to execute command checks and establish communication between the command
source and the disconnector. Using the control settings, you specify how the commands are to be processed
(see also chapter
8.3.1 Command Checks and Switchgear Interlocking Protection
Through the function SBO (Select Before Operate, reservation
37
), the switching device is reserved prior to the
actual switching operation, thus it remains locked for additional commands. Feedback monitoring provides
information about the initiator of the command while the command is in process, that means, informing
whether or not the command was implemented successfully. These two options can be selected individually in
the selection of the control model, so that 4 combinations in total are available (see the following table).
The control makes the following settings available (see next table).
Parameters
Default Setting Possible Parameter Values
(_:4201:101) Control model
SBO w. enh.
security
38
direct w. normal secur.
SBO w. normal secur.
direct w. enh. security
SBO w. enh. security
(_:4201:102) SBO time-out
30.00 s
-
(_:4201:103) Feedback monitoring time
10.00 s
-
(_:4201:104) Check switching authority
yes
no
yes
advanced
(_:4201:105) Check if pos. is reached
yes
no
yes
(_:4201:106) Check double activat. blk. yes
no
yes
Trigger Variants of the Disconnector
The activation types are identical to those for the circuit breaker. The meaning of abbreviations can be found
in
8.2.2.3 Connection Variants of the Circuit Breaker
8.2.2.3 Connection Variants of the Circuit Breaker
.
Whether the disconnector is triggered for 1-, 1.5-, or 2-phases depends on the design of the auxiliary and
control voltage system.
1-Pole Triggering
[dw1ptren-030211-01.tif, 1, en_US]
Figure 8-20
1-Pole Triggering
8.2.3.3
37
In the IEC 61850 standard, Reservation is described as Select before Operate (SBO).
38
This default setting is the standard control model for a switching command in an IEC 61850-compliant system.
Control Functions
8.2 Switching Devices
1100
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...