Parameter Value
Description
yes
With the setting
yes
, the dead time can be extended if after the expiration of
the dead time the circuit breaker is not ready for the next ON-OFF cycle. The
maximum delay of the dead time can be set with the parameter
(_:
6601:111) Max. dead-time extension
.
Siemens recommends this setting, if it can be assumed that the circuit breaker
becomes available to switch on the reclosing function only after an additional
waiting period.
Detailed information about the function can be found in Chapters
6.45.4.16 Circuit-Breaker Readiness
6.45.4.14 Closing Indication and Close Command
Parameter: Synchroch. aft. 3-pole d.t.
•
Default setting
(_:6571:110) Synchroch. aft. 3-pole d.t.
=
none
With the parameter
Synchroch. aft. 3-pole d.t.
you can determine if a synchrocheck must be
carried out for the configured automatic reclosing cycle.
If during a 3-pole interruption in the system stability problems may be a concern, the synchrocheck should be
carried out. If only 1-pole reclosure cycles are possible or stability problems are not to be expected during the
3-pole dead time, for example, due to a highly intermeshed system or radial system, please select the param-
eter
none
.
Parameter Value
Description
none
During the automatic reclosing cycle a synchrocheck is not executed.
internal
In the configured automatic reclosing cycle, a synchrocheck is executed after a
3-pole dead time prior to the close command of the circuit breaker.
For the synchrocheck a synchrocheck stage of the internal synchronization
function is used, which is contained in the same function group as the circuit
breaker and the automatic reclosing function. The selection of the synchro-
check stage that is used in the automatic reclosing cycle occurs through the
following described parameter Internal synchrocheck.
external
In the configured automatic reclosing cycle, a synchrocheck is executed after a
3-pole dead time prior to the close command of the circuit breaker.
An external synchrocheck device initiates the synchrocheck. The external
synchrocheck device is connected with the binary signals
Synchrocheck
request
and
>Release by ext.sync.
. Detailed information about the
function can be found in Chapter
6.45.4.14 Closing Indication and Close
under the section Synchrocheck.
Parameter: Internal Synchrocheck
These parameters are only significant if the previously described parameter
(_:6571:110) Synchroch.
aft. 3-pole d.t.
is set to
internal
.
With the parameter
Internal Synchrocheck
, you can determine which function block of the synchroniza-
tion function for the automatic reclosing function is used after a 3-pole dead time. This selection is only
possible for function blocks of the synchronization function, and which are included in the same circuit-
breaker function group as the automatic reclosing function. The setting options of the parameter will be
generated dynamically, according to the actual parameterization.
Protection and Automation Functions
6.45 Automatic Reclosing Function
932
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...