Siemens recommends using the default settings, which reflect common practice in Germany. Other national
transmission codes may require a slightly different range.
Parameter:
Time delay
•
Default setting
(_:13951:108) Time delay
=
0.00 s
You use the
Time delay
parameter to specify the minimum time delay for releasing the reconnection of the
power-generation facility after tripping by protection.
The setting depends on the specific application.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Reclos. stage
_:13951:1
Reclos. stage:Mode
•
off
•
on
•
test
off
_:13951:101
Reclos. stage:V>
threshold value
3.000 V to 340.000 V
95.000 V
_:13951:104
Reclos. stage:f difference
positive
0.01 Hz to 5.00 Hz
0.05 Hz
_:13951:105
Reclos. stage:f difference
negative
-5.00 Hz to -0.01 Hz
-2.50 Hz
_:13951:106
Reclos. stage:I> release
threshold
1 A @ 100 Irated 0.030 A to 10.000 A
0.100 A
5 A @ 100 Irated 0.15 A to 50.00 A
0.50 A
1 A @ 50 Irated
0.030 A to 10.000 A
0.100 A
5 A @ 50 Irated
0.15 A to 50.00 A
0.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
0.100 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
0.500 A
_:13951:108
Reclos. stage:Time delay
0.00 s to 3600.00 s
0.00 s
_:13951:102
Reclos. stage:Configura-
tion
Setting options depend on
configuration
Information List
No.
Information
Data Class
(Type)
Type
Reclos. stage
_:13951:81
Reclos. stage:>Block stage
SPS
I
_:13951:501
Reclos. stage:>V, f trip
SPS
I
_:13951:54
Reclos. stage:Inactive
SPS
O
_:13951:52
Reclos. stage:Behavior
ENS
O
_:13951:53
Reclos. stage:Health
ENS
O
_:13951:301
Reclos. stage:Release closure
ACT
O
6.40.4.3
6.40.4.4
Protection and Automation Functions
6.40 Undervoltage-Controlled Reactive-Power Protection
SIPROTEC 5, Overcurrent Protection, Manual
835
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...