Addr.
Parameter
C
Setting Options
Default Setting
_:16351:162
90V V.contr.gc:Power-
flow supervision
•
off
•
on
on
_:16351:163
90V V.contr.gc:Regulate
with T2 at start
•
off
•
on
on
_:16351:171
90V V.contr.gc:Set point
mode active
•
off
•
on
on
Line drop comp.
_:16351:125
90V V.contr.gc:Line drop
compensation
•
off
•
LDC-Z
•
LDC-XandR
off
_:16351:126
90V V.contr.gc:Target
voltage rising w1
0.0 % to 20.0 %
4.0 %
_:16351:147
90V V.contr.gc:Target
voltage rising w2
0.0 % to 20.0 %
4.0 %
_:16351:127
90V V.contr.gc:Max load
current
0.0 % to 500.0 %
100.0 %
_:16351:153
90V V.contr.gc:R line w1
0.0 Ω to 30.0 Ω
0.0 Ω
_:16351:154
90V V.contr.gc:X line w1
-30.0 Ω to 30.0 Ω
0.0 Ω
_:16351:155
90V V.contr.gc:R line w2
0.0 Ω to 30.0 Ω
0.0 Ω
_:16351:156
90V V.contr.gc:X line w2
-30.0 Ω to 30.0 Ω
0.0 Ω
Limiting
_:16351:102
90V V.contr.gc:Lower
tap-position limit
-128 to 127
1
_:16351:103
90V V.contr.gc:Higher
tap-position limit
-128 to 127
15
_:16351:128
90V V.contr.gc:Vmin
limiting
•
off
•
on
on
_:16351:129
90V V.contr.gc:Vmin
threshold w1
10.000 V to 340.000 V
105.000 V
_:16351:148
90V V.contr.gc:Vmin
threshold w2
10.000 V to 340.000 V
105.000 V
_:16351:130
90V V.contr.gc:Vmin
time delay
0 s to 20 s
10 s
_:16351:131
90V V.contr.gc:Vmax
limiting
•
off
•
on
on
_:16351:132
90V V.contr.gc:Vmax
threshold w1
10.000 V to 340.000 V
115.000 V
_:16351:149
90V V.contr.gc:Vmax
threshold w2
10.000 V to 340.000 V
115.000 V
_:16351:133
90V V.contr.gc:Vmax
time delay
0 s to 20 s
10 s
Blocking
_:16351:134
90V V.contr.gc:Blocking
behavior
•
Auto
•
Auto-Manual
Auto-Manual
_:16351:135
90V V.contr.gc:V<
Blocking
•
off
•
on
on
_:16351:136
90V V.contr.gc:V<
Threshold w1
10.000 V to 340.000 V
90.000 V
_:16351:150
90V V.contr.gc:V<
Threshold w2
10.000 V to 340.000 V
90.000 V
Control Functions
8.9 Voltage Controller
1230
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...