Determining the Time of the Ground-Fault Ignition
The algorithm uses the evaluation of the instantaneous values of the zero-sequence voltage to verify continu-
ously whether a ground fault occurred. This takes place regardless of whether the set threshold value for V0 is
exceeded. If a ground fault occurred, the measuring window for determining the direction is positioned and
the direction determination is performed. The position of the measuring window is logged via the indication
Pos. measuring window
(in FB General). The precise identification of the time T0 at which the ground
fault occurred is decisive for the correct direction determination.
Determination of Direction, Method of Measurement
The active energy of the zero-sequence system is calculated for the direction determination. Once the ground-
fault occurrence has been detected, the active energy will be calculated across approximately 1 cycle
frequency. If the active energy of the zero-sequence system is negative, a forward fault is present; otherwise it
is a backward fault.
Direction Result Message, Pickup
Determining the time of the ground-fault ignition and the direction is always done with maximum sensitivity.
With the parameter
V0> threshold value
, you define the sensitivity for the indication of the direction and
the pickup of the stage.
If the fundamental-component value of the zero-sequence voltage V0 exceeds the associated threshold value
(
V0> threshold value
parameter) within 100 ms after detecting the ground-fault ignition, the direction
result will be reported. In this way, high-impedance ground faults are also reported in which the zero-
sequence system values rise only slowly, and, for this reason, the occurrence of the ground fault is detected
noticeably earlier than the exceedance of the parameterized threshold value.
The direction result will be reported to the function via the
(_:2311:302) Ground fault
of the function
block General information. This indication is reported irrespective of the parameterized direction of the func-
tion.
If the determined direction corresponds with the parameterized direction (parameter
Directional mode
), a
pickup occurs.
Reset of the Algorithm
To allow a new directional measurement, the algorithm needs to be reset. The normal reset takes place when
the fundamental component of the zero-sequence voltage V0 drops below the V0 reset threshold. This reset
threshold is a small device-internal V0 threshold. It is also depending on an operational V0 and is thus a
dynamic threshold. The threshold value is 3.0 V secondary without dynamic influence.
Stabilization against Switching Operations
Switching operations in the system to be protected can cause transient signals in the zero-sequence system.
The stage is stabilized against possible overfunction due to switching operations.
Protection and Automation Functions
6.15 Sensitive Ground-Fault Detection
580
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...