
Where no time grading and therefore no displacement of the characteristic curve is required, leave the
Time
dial
parameter at
1
(default setting).
Parameter:
Reset
•
Default setting
(_:4891:131) Reset
=
disk emulation
You can use the
Reset
parameter setting to define whether the stage decreases according to the dropout
characteristic curve (in accordance with the behavior of a disk emulation = rotor disk) or instantaneously.
Parameter Value
Description
disk emulation
Select this setting if the device is coordinated with electromechanical
devices or other devices which perform a dropout after a disk emula-
tion.
instantaneous
Select this setting if the dropout does not have to be performed after a
disk emulation and an instantaneous dropout is desired instead.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:4891:1
Inverse-T 1:Mode
•
off
•
on
•
test
off
_:4891:2
Inverse-T 1:Operate &
flt.rec. blocked
•
no
•
yes
no
_:4891:111
Inverse-T 1:Directional
mode
•
forward
•
reverse
forward
_:4891:8
Inverse-T 1:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:4891:110
Inverse-T 1:Directional
comparison
•
no
•
yes
no
_:4891:112
Inverse-T 1:Release via
input signal
•
no
•
yes
no
_:4891:10
Inverse-T 1:Blk. by
meas.-volt. failure
•
no
•
yes
yes
_:4891:26
Inverse-T 1:Dynamic
settings
•
no
•
yes
no
_:4891:27
Inverse-T 1:Blk. w. inrush
curr. detect.
•
no
•
yes
no
_:4891:3
Inverse-T 1:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A
6.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.200 A
5 A @ 50 Irated
0.15 A to 175.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.000 A
_:4891:130
Inverse-T 1:Type of char-
acter. curve
_:4891:114
Inverse-T 1:Min. time of
the curve
0.00 s to 1.00 s
0.00 s
_:4891:131
Inverse-T 1:Reset
•
instantaneous
•
disk emulation
disk emulation
_:4891:101
Inverse-T 1:Time dial
0.00 to 15.00
1.00
_:4891:115
Inverse-T 1:Additional
time delay
0.00 s to 60.00 s
0.00 s
6.7.6.3
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground
466
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...