Addr.
Parameter
C
Setting Options
Default Setting
Dyn.set: bin.input
_:34
User curve #:Effected by
binary input
•
no
•
yes
no
_:41
User curve #:Stage
blocked
•
no
•
yes
no
_:19
User curve #:Threshold
1 A @ 100 Irated 0.010 A to 35.000 A
1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A
6.00 A
1 A @ 50 Irated
0.010 A to 35.000 A
1.200 A
5 A @ 50 Irated
0.05 A to 175.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.002 A to 8.000 A
6.000 A
_:107
User curve #:Time dial
0.05 to 15.00
1.00
Information List
No.
Information
Data Class
(Type)
Type
User curve #
_:81
User curve #:>Block stage
SPS
I
_:500
User curve #:>Block delay & op.
SPS
I
_:54
User curve #:Inactive
SPS
O
_:52
User curve #:Behavior
ENS
O
_:53
User curve #:Health
ENS
O
_:60
User curve #:Inrush blocks operate
ACT
O
_:59
User curve #:Disk emulation running
SPS
O
_:55
User curve #:Pickup
ACD
O
_:56
User curve #:Operate delay expired
ACT
O
_:57
User curve #:Operate
ACT
O
Blocking of the Tripping by Device-Internal Inrush-Current Detection
Description
With the
Blk. w. inrush curr. detect.
parameter, you can define whether tripping of the stage
should be blocked when a threshold value is exceeded due to an inrush current. In case of a blocking, the
stage picks up. The start of the tripping delay and the trip signal are blocked. The function signals this through
a corresponding indication. If the blocking drops out and the threshold value of the stage is still exceeded, the
time delay is started. After that time, the stage operates. The following figure only shows the part of the stage
(exemplified by definite-time overcurrent protection stage 1) that illustrates the influence of the inrush-
current detection. Only if the central function Inrush-current detection (see section
) is in effect can the blocking be set.
6.5.6.4
6.5.7
6.5.7.1
Protection and Automation Functions
6.5 Overcurrent Protection, Ground
402
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...