Cold-Load Pickup Detection (Optional)
Logic
[loprocls-180912-01.tif, 1, en_US]
Figure 5-94
Logic Diagram of the Cold-Load Pickup Detection Function Block
The Cold-load pickup detection function block detects that a specific time has been exceeded after deactiva-
tion of the line or protected object. If you want to connect the protected object again, you must note that an
increased load-current requirement exists for a limited time after connection. This results from the nature of
the load.
The Cold-load pickup detection function block ensures that different parameters are used for an adjustable
time after connection. For example, for the time of the
Min. CB-open time
parameter, you can increase
the threshold value of a protection function or you can select a special characteristic curve.
If the Cold-load pickup detection function block detects an open feeder and the set time of the
Min. CB-
open time
parameter has expired, the indication
>Activate cold-load
is generated.
With the
>Activate cold-load
indication, you can activate a parameter set of the Cold-load pickup func-
tion. Via the binary input signal
>Activate cold-load
, you can also activate the
>Activate cold-load
indication directly.
If the Cold-load pickup detection function block detects closure and the corresponding load current, it starts
the time set in the
Dropout delay CB closed
parameter. The
>Activate cold-load
indication and
the activated parameter set are deactivated after this time has elapsed.
5.8.8
Function-Group Types
5.8 Process Monitor
298
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...