The following figure shows 2 application scenarios of protection devices with the Underfrequency load shed-
ding function.
[dw_UFLS_positive power direction, 1, en_US]
Figure 6-217
Application Scenarios
Dotted arrow: Standard forward direction of the protection functionality
Solid arrow:
Positive active-power flow direction
The standard forward direction of the protection functionality is from the busbar to the protected object which
is the transformer for device 1 or the feeder for device 2. The standard forward direction of the protection
functionality is configured via the
(_:8881:116) Neutr.point in dir.of ref.obj
parameter of the
measuring point I-3ph (see chapter
6.1.4 Application and Setting Notes for Measuring Point Current 3-Phase
). For the load-shedding function, the positive active-power flow direction can differ from the standard
forward direction of the protection functionality, such as for device 1. To adapt the function to this condition,
the
Positive power direction
parameter is used. With the
Positive power direction
parameter,
you can set the positive active-power flow direction either to the same as or to the inverse of the standard
forward direction.
•
For device 1, set the
Positive power direction
parameter to
inv. to CT neu.pnt sett.
.
Then, the positive active-power flow direction of the power criterion is opposite to the standard forward
direction of the protection functionality. Consequently, the Underfrequency load shedding function
sheds the medium-voltage busbar when the positive power-flow direction is from the high-voltage
busbar to the medium-voltage busbar.
•
For device 2, set the
Positive power direction
parameter to
acc. to CT neu.pnt sett.
.
Then, the positive active-power flow direction of the power criterion is the same as the standard forward
direction of the protection functionality. Consequently, the Underfrequency load shedding function
sheds the feeder when the positive power-flow direction is from the medium-voltage busbar to the
feeder.
Protection and Automation Functions
6.34 Underfrequency Load Shedding
778
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...