Name
Type
Description
Control: Reset memory
SPC
Delete all recording via the function key. The
error numbers are reset.
Control: Delete memory
SPC
Delete all recording via the function key. The
error numbers remain as is.
Control: >External start
SPS
Start recording by an external binary signal, for
example, by the trip command of an external
protection device. The set pre and post-trigger
time are taken into account.
Control: >Manual start
SPS
Start a recording of fixed duration (parameter
Manual record time
) by way of an
external binary signal, for example, manually via
the function key or by an external binary signal.
In the following table, you can find output signals of the Fault recorder function:
Name
Type
Description
General: Mode
ENC
Status feedback of the fault recording according
to chapter
General: State
ENS
General: Standby
ENS
Control: Error number
INS
The indication of the current error number
allows a unique allocation of entries in the
message buffers for the recorded fault records.
Control: Recording started
SPS
Fault recording running
Application and Setting Notes
Parameter: Fault recording
•
Recommended setting value
(_:2761:130) Fault recording
=
with pickup
With the
Fault recording
parameter, you define the time interval at which faults are recorded. The total
record duration is defined as the duration of the fault plus the total of the parameters
Pre-trigger time
,
Post-trigger time
and is limited by the maximum record duration.
Parameter Value
Description
with pickup
The fault recording time is determined by the total number of all protection
pickups. The resulting pickup signals of all function groups are taken into
account.
Note: When the post-trigger time has expired, the indications of an auto-
matic reclosing function are not recorded. Evolving faults after expiry of the
post-trigger time can result in the opening of a new fault with its own
recording.
with pickup & AR cyc.
The fault recording time is determined by the total number of all protection
pickups including short and long interruptions (automatic reclosing cycles).
It includes the resulting pickup signals of all function groups and the
runtimes of initiated automatic reclosing cycles for all active automatic
reclosing functions.
user-defined
The fault recording time is defined user-specific.
Note: You must specify all signals for individual definition of the fault
recording time in the DIGSI 5 information-routing matrix. In the information
routing matrix in the Fault record column, the fault recording has for this
purpose a separate column Trigger. The record duration is calculated from
the logical OR operation of all initiated, configured signals.
3.4.4
System Functions
3.4 Fault Recording
SIPROTEC 5, Overcurrent Protection, Manual
107
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...