In the following, certain settings are explained that are necessary for this application (detection of intermittent
ground faults):
•
Parameter:
(_:2311:102) Dropout delay
The function must treat the intermittent process as one ground fault. For this, it is necessary that the
indication
Ground fault
does not drop out between 2 consecutive current peaks. This is ensured via
the
Dropout delay
parameter (FB General). A dropout delay of 1 s is a feasible value.
•
Parameter:
(_:12601:104) Dir. determination delay
You must set the delay of the direction determination to 0 s so that the direction of the current peaks can
be determined.
•
Parameter:
(_:12601:105) α1 reduction dir. area
and
(_:12601:106) α2 reduction
dir. area
The current peaks show a clear ohmic component. With these parameters, you can limit the direction
characteristic and ensure a reliable direction result.
Siemens recommends setting both parameters to 10°.
•
Parameter:
(_:12601:110) Blk. after fault extinction
To make possible a continuous and immediate detection of the current peaks, you must switch off the
blocking after fault suppression.
No further parameters need particular consideration with regard to an intermittent ground fault. You can set
these as for the detection of permanent ground faults.
Directional 3I0 Stage with φ(V0,3I0) Measurement
Description
Logic
[logfppvi-291112-02.vsd, 1, en_US]
Figure 6-133
Logic Diagram of the Stage Control
6.15.7
6.15.7.1
Protection and Automation Functions
6.15 Sensitive Ground-Fault Detection
586
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...