Addr.
Parameter
C
Setting Options
Default Setting
_:13831:2
Definite-T 1:Operate &
flt.rec. blocked
•
no
•
yes
no
_:13831:3
Definite-T 1:Threshold
0.80 p.u. to 10.00 p.u.
5.00 p.u.
_:13831:6
Definite-T 1:Operate
delay
0.01 s to 3600.00 s
0.03 s
Information List
No.
Information
Data Class
(Type)
Type
General
_:2311:301
General:VpeakA
MV
O
_:2311:302
General:VpeakB
MV
O
_:2311:303
General:VpeakC
MV
O
Group indicat.
_:4501:55
Group indicat.:Pickup
ACD
O
_:4501:57
Group indicat.:Operate
ACT
O
Definite-T 1
_:13831:81
Definite-T 1:>Block stage
SPS
I
_:13831:54
Definite-T 1:Inactive
SPS
O
_:13831:52
Definite-T 1:Behavior
ENS
O
_:13831:53
Definite-T 1:Health
ENS
O
_:13831:55
Definite-T 1:Pickup
ACD
O
_:13831:56
Definite-T 1:Operate delay expired
ACT
O
_:13831:57
Definite-T 1:Operate
ACT
O
Stage with User-Defined Characteristic Curve
Description
This stage is structured the same way as the stage with a voltage-dependent characteristic (see chapter
). The only difference is that you can define the characteristic curve as desired. This means
that you can also define a dropout characteristic curve. This makes the dropout delay parameter superfluous
and unneeded.
User-Defined Characteristic Curve
With the user-defined characteristic curve, you can define the operate curve point by point using up to 30
value pairs of voltage and time. The device uses linear interpolation to calculate the characteristic curve from
these values. You can also define a dropout characteristic curve if you wish.
Pickup and Dropout Behavior with the User-Defined Characteristic Curve
If the measurand Û/V
C-rated
(t) exceeds the threshold value, the characteristic is followed. An integrating
method of measurement summarizes the weighted time. The weighted time results from the characteristic
curve. This means that the time associated with the present measured value is determined from the character-
istic curve. Once the weighted time exceeds the value 1, the stage operates.
If the measured value falls below 95 % of the set threshold value, the dropout is initiated. The pickup will be
indicated as clearing. The weighted time results from the dropout characteristic curve. The integral value is
reduced until it reaches 0.
7.6.4.4
7.6.5
7.6.5.1
Capacitor Bank Protection
7.6 Peak Overvoltage Protection for Capacitors
SIPROTEC 5, Overcurrent Protection, Manual
1029
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...