EXAMPLE
[forbala2-290812-02.tif, 1, en_US]
Max. continuously perm. I
2
= 10.0 % (corresponds to 0.1)
Unbalanced load factor K
= 15 s
Cooling time therm. replica
= 1500 s
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Therm. Stage 1
_:11011:1
Therm. Stage 1:Mode
•
off
•
on
•
test
off
_:11011:2
Therm. Stage 1:Operate &
flt.rec. blocked
•
no
•
yes
no
_:11011:101
Therm. Stage 1:Max.
continuously perm. I2
3.0 % to 30.0 %
10.0 %
_:11011:102
Therm. Stage 1:Unbalanced
load factor K
1.0 s to 100.0 s
15.0 s
_:11011:103
Therm. Stage 1:Cooling
time therm.replica
0 s to 50000 s
1500 s
_:11011:104
Therm. Stage 1:Warning
delay
0.0 s to 60.0 s;∞
15.0 s
Information List
No.
Information
Data Class
(Type)
Type
Group indicat.
_:4501:55
Group indicat.:Pickup
ACD
O
_:4501:57
Group indicat.:Operate
ACT
O
Therm. Stage 1
_:11011:81
Therm. Stage 1:>Block stage
SPS
I
_:11011:501
Therm. Stage 1:>Reset thermal replica
SPS
I
_:11011:53
Therm. Stage 1:Health
ENS
O
_:11011:54
Therm. Stage 1:Inactive
SPS
O
_:11011:52
Therm. Stage 1:Behavior
ENS
O
_:11011:302
Therm. Stage 1:Thermal replica reset
SPS
O
_:11011:301
Therm. Stage 1:Warning
ACD
O
_:11011:55
Therm. Stage 1:Pickup
ACD
O
_:11011:56
Therm. Stage 1:Operate delay expired
ACT
O
_:11011:57
Therm. Stage 1:Operate
ACT
O
_:11011:303
Therm. Stage 1:ΘI2/Θop
MV
O
6.22.5
6.22.6
Protection and Automation Functions
6.22 Unbalanced-Load Protection
SIPROTEC 5, Overcurrent Protection, Manual
691
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...