the device switches to another channel (etc.). Once switched to a current channel, the system automatically
switches back to the voltage channel if a voltage channel is valid again.
Parameter Value
Description
inactive
If the channels of the measuring point are not to be considered for deter-
mining the sampling frequency, please select the setting value
inactive
.
active
If you have set the parameter
Tracking
=
active
, the measuring point
will be included when determining the sampling frequency.
Note: If the parameter
Tracking
=
active
, the determined sampling
frequency applies to all functions in the device not using fixed sampling
rates.
Parameter: Magnitude correction
•
Default setting
(_:3811:103) Magnitude correction
=
1.000
When using the
Magnitude correction
parameter, the magnitude (magnitude correction) is adjusted for
the voltage input. This allows you to correct the tolerances of the primary current transformer phase-selec-
tively. The magnitude correction may be required for highly precise measurements. Use a comparison meas-
urement to determine the setting value (for example, with a high-precision measuring-voltage transformer). If
a primary correction is not necessary, retain the default setting.
i
i
NOTE
The
Magnitude correction
parameter has nothing to do with the internal adjustment of the input
circuit.
Settings
General Information
Addr.
Parameter
C
Setting Options
Default Setting
General
_:2311:101
General:Phase sequence
•
ABC
•
ACB
ABC
Measuring Point I-3ph
Addr.
Parameter
C
Setting Options
Default Setting
General
_:8881:115
CT 3-phase:CT connec-
tion
•
not assigned
•
3-phase + IN
•
3-phase
•
3-phase + IN-separate
•
3-phase, 2 primary CT
•
2
3ph,2prim.CT + IN-sep
•
2ph, 2p. CT + IN-sep
3-phase + IN
_:8881:127
CT 3-phase:Tracking
•
inactive
•
active
active
_:8881:130
CT 3-phase:Measuring-
point ID
0 to 100
0
CT phases
_:8881:101
CT 3-phase:Rated
primary current
1.0 A to 100 000.0 A
1000.0 A
6.1.8
Protection and Automation Functions
6.1 Power-System Data
312
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...