Application Notes for Directional Comparison Protection
The direction determination of directional overcurrent protection can be used to implement directional
comparison protection for cable runs with infeed at both ends. Directional comparison protection is used for
the selective isolation of a faulted line section (for example, subsections of closed rings). Sections are isolated
in fast time, that is, they do not suffer the disadvantage of long grading times.
This technique requires that directional information can be exchanged between the individual protection
stations. You can implement this information exchange using a communication channel (protection interface
or IEC 61850 GOOSE) or with pilot wires for signal transmission via an auxiliary voltage loop.
Protection Principle
The protection principle is shown in
. 2 devices (one at the start of the line and the other at the
end of the line) work together in each line section. The information fault in forward direction is transferred
between them. A directional definite-time overcurrent protection level is in operation in both devices in the
forward direction (1st level). However, this level is not enabled in the idle state. The level is only released
when the information fault in forward direction is received from the opposite end. If the enabled level also
defines the fault in the forward direction, the fault must be on this line section and the level trips immediately.
As this protection principle works with an enable procedure (and not with a blocking procedure), there is no
need to delay the level.
A second directional definite-time overcurrent protection stage with standard time grading works in parallel
with the first stage as a selective backup stage. This ensures full selectivity of protection in the following situa-
tions:
•
Infeed at one end or weak infeed at one end: In this case, no release signal is generated.
•
Failure of the communication route: In this case, the release signal is not transmitted.
To provide selective protection in fast time for busbars between the line sections also, you can combine this
protection principle with the principle of reverse interlocking. This principle is not discussed in further detail in
this document.
[dwdocp07-240611-01.tif, 2, en_US]
Figure 6-60
Selectivity through Directional Comparison Protection
Stage ▶:
▶, ◀:
Stage is set in the forward direction; stage 1 is instantaneous, stage 2 is graded
If a threshold value is exceeded, the stage indicates the direction (forward or reverse)
If you are using a communication channel, the protocol-transmission methods detect if the channel is inter-
rupted. If you are using pilot wires, we recommend operation based on a closed-circuit connection. The device
uses a function chart to check and indicate if the binary input is dead for an unexpectedly long period. In
6.6.10
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases
438
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...