Addr.
Parameter
C
Setting Options
Default Setting
_:14011:142
90V V.contr.2w:I<
Threshold
3 % to 100 %
10 %
_:14011:143
90V V.contr.2w:I< Time
delay
0 s to 20 s
10 s
Three-Winding Transformer
Addr.
Parameter
C
Setting Options
Default Setting
Winding 1
_:2311:101
General:Rated current
0.20 A to 100000.00 A
1000.00 A
_:2311:103
General:Rated voltage
0.20 kV to 1200.00 kV
400.00 kV
Winding 2
_:2311:102
General:Rated current
0.20 A to 100000.00 A
1000.00 A
_:2311:104
General:Rated voltage
0.20 kV to 1200.00 kV
400.00 kV
_:2311:106
General:Rated apparent
power
-1.00 MVA to -1.00 MVA
0.00 MVA
Tap changer
_:13981:111
Tap changer:Maximum
output time
0.02 s to 1800.00 s
1.50 s
_:13981:112
Tap changer:Supervision
behavior
•
off
•
warning
•
alarm block
alarm block
_:13981:113
Tap changer:Motor
supervision time
5 s to 100 s
10 s
_:13981:116
Tap changer:Highest tap
changer pos.
•
Lowest voltage tap
•
Highest voltage tap
Lowest voltage
tap
_:13981:114
Tap changer:Lowest tap
position
-64 to 64
1
_:13981:115
Tap changer:Highest tap
position
-64 to 64
15
General
_:15601:1
90V V.contr.3w:Mode
•
off
•
on
•
test
on
_:15601:101
90V V.contr.3w:Oper-
ating mode
•
Manual
•
Auto
Manual
_:15601:157
90V V.contr.3w:Winding
selection
•
Winding 1
•
Winding 2
•
WithMaxLoad
Winding 1
Control
_:15601:107
90V V.contr.3w:Check
switching authority
•
no
•
yes
yes
_:15601:109
90V V.contr.3w:Control
model
•
direct w. normal secur.
•
SBO w. normal secur.
•
direct w. enh. security
•
SBO w. enh. security
SBO w. enh.
security
_:15601:110
90V V.contr.3w:SBO
time-out
0.01 s to 1800.00 s
30.00 s
_:15601:111
90V V.contr.3w:Feed-
back monitoring time
0.01 s to 1800.00 s
10.00 s
Control Functions
8.9 Voltage Controller
SIPROTEC 5, Overcurrent Protection, Manual
1225
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...