Parameter: Minimum operate time
•
Default setting
(_:112) Minimum operate time
=
-
The
Minimum operate time
parameter is used to set the minimum duration for tripping the function.
!
CAUTION
Do not set a time that is too short.
If you set a time that is too short, there is a danger (dropout of the function without the current-flow
criterion) that the device contacts will interrupt the control circuit. If this happens, the device
contacts will burn out.
²
Set a duration that is long enough to ensure that the circuit breaker reaches its final position open
reliably after a control operation.
Input Signal: >CB defect
The input signal
>CB defect
has a default filtering time of 20 ms. This filtering time prevents the input
signal from becoming effective in the case of a transient activation of the physical binary input, which can be
caused by the pressure change when the CB opens.
This time can be set to 0 if such a transient pickup of the physical binary input can be excluded due to the CB
design.
Output Signal: Retrip T1
If only one control circuit is available for the local CB, it is not mandatory to route the output signal because
the signal also controls the CB trip logic.
If a 2nd Control circuit is present, the
Retrip T1
output signal must be routed to the associated binary
output.
Output Signal: Trip T2
In order to operate the adjacent circuit breakers, the backup tripping (indication
Trip T2
) must be routed to
a binary output; andif necessary, to an interface (intertripping to opposite end).
Settings
Addr.
Parameter
C
Setting Options
Default Setting
50BF Ad.CBF #
_:1
50BF Ad.CBF #:Mode
•
off
•
on
•
test
on
_:105
50BF Ad.CBF #:Holding
int. start signal
•
no
•
yes
yes
_:107
50BF Ad.CBF #:Start via
binary input
•
no
•
2 channel
•
1 channel
no
_:106
50BF Ad.CBF #:Holding
ext. start signal
•
no
•
yes
no
_:111
50BF Ad.CBF #:Sup.time
for release signl
0.00 s to 1.00 s
0.06 s
_:103
50BF Ad.CBF #:CB
aux.cont. crit. allowed
•
no
•
w. 'CB pos. closed 3p.'
no
6.41.5
Protection and Automation Functions
6.41 Circuit-Breaker Failure Protection
850
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...