Settings
Addr.
Parameter
C
Setting Options
Default Setting
Inverse-T #
_:1
Inverse-T #:Mode
•
off
•
on
•
test
off
_:2
Inverse-T #:Operate &
flt.rec. blocked
•
no
•
yes
no
_:10
Inverse-T #:Blk. by
meas.-volt. failure
•
no
•
yes
yes
_:9
Inverse-T #:Measured
value
•
phase-to-ground
•
phase-to-phase
phase-to-phase
_:8
Inverse-T #:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:101
Inverse-T #:Pickup mode
•
1 out of 3
•
3 out of 3
1 out of 3
_:102
Inverse-T #:Pickup delay
•
no
•
yes
no
_:3
Inverse-T #:Threshold
0.300 V to 175.000 V
80.000 V
_:109
Inverse-T #:Pickup factor
0.80 to 1.00
0.90
_:103
Inverse-T #:Charact.
constant k
0.00 to 300.00
1.00
_:104
Inverse-T #:Charact.
constant α
0.010 to 5.000
1.000
_:105
Inverse-T #:Charact.
constant c
0.000 to 5.000
0.000
_:106
Inverse-T #:Time dial
0.05 to 15.00
1.00
_:107
Inverse-T #:Additional
time delay
0.00 s to 60.00 s
0.00 s
_:108
Inverse-T #:Reset time
0.00 s to 60.00 s
0.00 s
Information List
No.
Information
Data Class
(Type)
Type
Inverse-T #
_:81
Inverse-T #:>Block stage
SPS
I
_:54
Inverse-T #:Inactive
SPS
O
_:52
Inverse-T #:Behavior
ENS
O
_:53
Inverse-T #:Health
ENS
O
_:55
Inverse-T #:Pickup
ACD
O
_:300
Inverse-T #:Pickup loop AB
SPS
O
_:301
Inverse-T #:Pickup loop BC
SPS
O
_:302
Inverse-T #:Pickup loop CA
SPS
O
_:56
Inverse-T #:Operate delay expired
ACT
O
_:57
Inverse-T #:Operate
ACT
O
6.29.4.3
6.29.4.4
Protection and Automation Functions
6.29 Undervoltage Protection with 3-Phase Voltage
SIPROTEC 5, Overcurrent Protection, Manual
749
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...