Parameter Value
Description
I
2
/I
rated, obj
The negative-sequence current is referred to the rated current of the
protected object. This is a preferred normalization for electrical machines,
because the permissible limiting values are indicated exclusively referred to
the machine rated current. You can also use this normalization for other
applications.
I
2
/I
1
The normalization of the negative-sequence system to the positive-
sequence system yields a higher sensitivity. Use this normalization when
detecting interruptions in the primary system.
Set the parameter depending on the application.
Parameter:
Current limitation Imax
,
Maximum phase current
•
Default setting
(_:2311:107) Current limitation Imax
=
no
•
Recommended setting value
(_:2311:101) Maximum phase current
=
10.0 A at 1 A
If the protection function needs a maximum current limitation, set the value of the
Current limitation
Imax
parameter from
no
to
yes
. With the parameter
Maximum phase current
, you set the upper limit of
the phase current. CT saturation will cause negative-sequence current in the secondary system. To avoid over-
function due to the CT saturation, a suitable phase-current limit value is 10 times of the rated protection-
object current.
Parameter:
Release current
•
Recommended setting value
(_:2311:104) Release current
=
0.05 A at 1 A
For the safe calculation of negative-sequence currents, the current in at least one phase must be greater than
5 % of the secondary rated device current. For a 1-A device, the value of
Release current
is 0.05 A (0.25 A
for a 5-A device).
Protection and Automation Functions
6.17 Negative-Sequence Protection
SIPROTEC 5, Overcurrent Protection, Manual
635
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...