Error Description
Status Health
A communication module has not received any more
data from the RTD unit for 9 sec.
Warning
The
Failure
signal is set as soon as one of the sensor function blocks reports a failure.
Application and Setting Notes
Parameter: Port
•
Default setting
(_:2311:103) Port
=
port J
Use the
Port
parameter to define over which port the external RTD unit is connected to the SIPROTEC 5
device.
If you want to connect the external RTD unit to the integrated Ethernet interface, set the parameter
Port
=
Port J
. If you want to connect the external RTD unit to an Ethernet plug-in module, set the parameter
Port
=
Port F
,
Port E
,
Port P
, or
Port N
.
You can connect directly the RTD unit to the device via the internal 10-Mbit Ethernet port J. If you operate the
RTD unit on another port via a 100-Mbit communication module, you need an interconnected 10/100-Mbit
autosensing switch, which adapts transmission rates accordingly.
Parameter: IP address
•
Default setting
(_:2311:104) IP address
=
10.16.60.1
With the
IP address
parameter, you set the IP address of the RTD unit connected to the communication
module via the SUP protocol. Every RTD unit has to be assigned a unique IP address. The IP address to be set
depends on your network configuration. You can set any valid IPv4 address that does not cause conflicts with
other IP addresses in the network. Set an appropriate IP address first at the Ziehl TR1200 IP RTD unit. Then
specify the
IP address
parameter for the communication module to the same address.
Settings on the RTD Unit
The Ziehl TR1200 IP RTD unit is set with the front keys or in a Web browser on a laptop computer via its
Ethernet interface. Set the connection type of the sensors (3-wire connection or resistance value for 2-wire
connection), the idle state of the fault-indication relay, as well as the IP interface setting.
The code lock has to be switched off for parameterization. This is only possible using the front keys of the RTD
unit. The code lock is off (switched off) in as-delivered condition and has pin 504.
For detailed information on the settings, refer to the TR1200 IP manual that comes with the RTD unit. The
documents are also available in the SIPROTEC download area (http://www.siprotec.de) under Accessories ->
7XV5662-xAD.
For an Ethernet connection to a SIPROTEC 5 device communicating with the RTD unit TR1200 IP via the SUP
protocol (Slave Unit Protocol), the
Modbus TCP
setting must be activated in the RTD unit. You can activate
the Modbus TCP protocol using the function keys under the TcP - mod menu item or with the Web browser in
the TCP/UDP Config tab. The RTD (RTD protocol) and UDP Port settings have no effect here. The Modbus TCP
port is permanently set to 502 and cannot be changed.
5.6.7.4
Function-Group Types
5.6 Function-Group Type Analog Units
264
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...