[dw_tilt-power reactive power, 2, en_US]
Figure 6-233
Tilt-Power Characteristic
Pickup
The stage compares the selected power value with the set
Threshold
. Depending on the stage type (Power
Q> or Power Q<) being above or falling below the threshold value will lead to a pickup.
Dropout Delay
A delay can be set for the dropout when the measured value falls below the dropout threshold. The pickup is
maintained for the specified time. The time delay of the tripping (parameter
Operate delay
) continues to
run. Once the
Operate delay
has elapsed, the stage trips.
Blocking the Stage
In the event of blocking, the picked up stage will be reset. Blocking the stage is possible externally or internally
via the binary input signal
>Block stage
.
Application Example
The setting of the function will be explained using an active/reactive power range as an example. If the appa-
rent power phasor is within the power range (in
tripping zone defined by characteristics), an
alarm indication is generated. For this purpose, you have to make an AND operation of the stage indications of
the active and reactive power stage in CFC. The function used is 3-phase power measurement.
shows the threshold values and the location of the characteristics in the PQ diagram.
6.37.5
Protection and Automation Functions
6.37 Power Protection (P,Q), 3-Phase
SIPROTEC 5, Overcurrent Protection, Manual
803
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...