Overfrequency-Protection Stage
Logic of a Stage
[lostofqp-040411-01.tif, 1, en_US]
Figure 6-210
Logic Diagram of the Overfrequency-Protection Stage
Frequency-Measurement Method
Overfrequency protection is available in 2 functional configurations. These work with different frequency-
measurement methods. You select the frequency-measurement method in dependence of the application.
•
Angle-difference method (method A):
The angle-difference method determines the phasor of the positive-sequence voltage in multiphase
systems. In the case of 1-phase connection, it always processes the phasor of the connected voltage.
Since the change of angle of the voltage phasor over a given time interval is proportional to the
frequency change, the current frequency can be derived from it.
•
Filtering method (method B):
The filtering method processes the instantaneous voltage values and determines the current frequency
using a suitable combination of filters. The frequency-protection function selects automatically the
largest voltage as the measurand. In a multiphase connection, the phase-to-phase voltage is always the
largest. If in a multiphase connection the selected voltage is no longer available, the function changes
over automatically to the next maximum voltage. The function can even operate with just one voltage.
6.32.3
Protection and Automation Functions
6.32 Overfrequency Protection
764
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...