[dwfehler-291112-01.tif, 1, en_US]
Figure 6-270
Behavior under Different Fault Conditions
Functional Measured Values
Measured Value
Description
(_:306) I REF,operate
Operate quantity of the restricted ground-fault protection from
the angle criterion
(_:307) I Angle,REF
Stabilizing value (angle) of the restricted ground-fault protection
from the angle criterion
(_:311) I REF,Trip operate
Operate quantity of the restricted ground-fault protection when
OFF
(_:312) I angle,REF operate
Stabilizing value of the restricted ground-fault protection when
OFF
(_:301) I diff.
Differential current
(_:302) I restr.
Restraint current
You will find the measured values for the Restricted ground-fault protection under the following device
menu entries:
•
Main menu → Measurements → function → Function values → 87N REF
Application and Setting Notes
i
i
NOTE
The following conditions must be observed when setting the threshold values:
Threshold value ≥ max {
0.05 I/Irated,S
;
0.05 I/Irated,S
* I
prim transf. max
/ I
rated, protected object
}
Threshold value ≤ min {
2.00 I/Irated,S
;
100.00 I/Irated,S
* I
prim transf. max
/ I
rated, protected object
}
The value
0.05 I/Irated,S
is the minimum possible setting value and
2.00 I/Irated,S
the
maximum possible. I
prim,transf. max
is the largest transformer current and I
rated,protected object
the protected object
rated current.
100.00 I/Irated,S
is the upper measurement limit.
If otherwise, it could happen that there is chattering of the pickup indication, the minimum threshold limit
is lifted. The maximum limit on the other hand is corrected downward, if the exceeding current otherwise
through the magnitude scaling must be so large, that it would already be outside of the measuring range
of the transformer.
The adaptation of the setting limits is done automatically. In addition, a setting is prevented outside of
these limits.
6.43.4
Protection and Automation Functions
6.43 Restricted Ground-Fault Protection
868
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...