51
Specifications
Section 2-2
I/O Terminal Blocks of CPU Units with 20 I/O Points
Input Terminal Block (Top Block)
Setting Input Functions Using PLC Setup
Address
Input operation settings
High-speed counters
Origin searches
Word
Bit
Normal
inputs
Interrupt
inputs
(See note.)
Quick-
response
inputs
Operation settings:
High-speed counters enabled
Phase-Z reset
Origin searches
enabled for pulse
outputs 0 and 1
Single-phase
(increment
pulse input)
Two-phase (differential
phase x4, up/down, or
pulse/direction)
CIO 0
00
Normal
input 0
---
---
Counter 0,
increment input
Counter 0, A phase, up,
or count input
---
01
Normal
input 1
---
---
Counter 1,
increment input
Counter 0, B phase,
down, or direction input
---
02
Normal
input 2
---
---
Counter 2,
increment input
Counter 1, A phase, up,
or count input
---
03
Normal
input 3
---
---
Counter 3,
increment input
Counter 1, B phase,
down, or direction input
---
04
Normal
input 4
Interrupt
input 0
Quick-
response
input 0
Counter 0,
phase-Z/reset
input
Counter 0, phase-Z
reset input
---
05
Normal
input 5
Interrupt
input 1
Quick-
response
input 1
Counter 1,
phase-Z reset
input
Counter 1, phase-Z
reset input
---
06
Normal
input 6
Interrupt
input 2
Quick-
response
input 2
Counter 2,
phase-Z reset
input
---
Pulse output 0: Origin
input signal
07
Normal
input 7
Interrupt
input 3
Quick-
response
input 3
Counter 3,
phase-Z reset
input
---
Pulse output 1: Origin
input signal
08
Normal
input 8
Interrupt
input 4
Quick-
response
input 4
---
---
09
Normal
input 9
Interrupt
input 5
Quick-
response
input 5
---
---
10
Normal
input 10
---
---
---
Pulse output 0: Origin
proximity input signal
11
Normal
input 11
---
---
---
Pulse output 1: Origin
proximity input signal
L1
L2/N COM
01
03
05
07
09
11
00
02
04
06
08
10
AC Power Supply Models
Inputs (CIO 0)
DC Power Supply Models
COM
01
03
05
07
09
11
00
02
04
06
10
08
+
−
NC
Inputs (CIO 0)
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...