363
Serial Communications
Section 6-3
PLC Setup
PT System Menu
Set the PT as follows:
1,2,3...
1.
Select NT Link (1:N) from Comm. A Method or Comm. B Method on the
Memory Switch Menu under the System Menu on the PT Unit.
2.
Press the SET Touch Switch to set the Comm. Speed to High Speed.
6-3-8
1:1 NT Links
The NT Link communications protocol was developed to enable high-speed
communications between PLC and Programmable Terminals (PTs). There are
two communications modes supported by the NT Link protocol: 1:1 NT Links,
in which one PLC is connected to one PT, and 1:N NT Links, in which one
PLC is connected to more than one PT.
Connections
With the NT Link protocol, the PLC auto-
matically responds to commands sent
from the PT, so no communications pro-
gramming is required in the CP1L.
Port
Name
Settings contents
Default values
Other conditions
Serial port
1 or 2
Mode: Communications mode NT Link (1:N): 1:N NT Links Host Link
Turn OFF pin 4 on the CPU
Unit DIP switch hen using
serial port 1 and turn OFF pin
5 when using serial port 2.
Baud: Baud rate
38,400 (standard)
115,200 (high speed)
9,600
(disabled)
NT/PC Link Max:
Highest unit number
0 to 7
0
---
OMRON PT
NT Link
RS-232C
CP1L
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...