293
Inverter Positioning
Section 5-3
Use the following for the present values of the internal pulse and error counter
of inverter positioning.
A36
07
Error Counter Alarm
Flag
ON: Error counter
alarm
OFF: No error
counter alarm
Turned ON at following times:
• When pulse output to error counter is
stopped and absolute value of error
counter present value is greater than
or equal to error counter alarm detec-
tion value
Turned OFF at following times:
• When error counter alarm is reset
• When power to CPU Unit is turned ON
• When CPU Unit operation starts
• When CPU Unit operation stops
This flag can be
used to provide
notification of
excessive pulses in
the error counter,
e.g., when encoder
wiring breaks dur-
ing positioning.
08 to 14 Not used.
15
Inverter Positioning
Output Value Sign
Flag
ON:
OFF:
Turned ON at following times:
• When signed output value is between
0000 0000 and 7FFF FFFF hex.
Turned OFF at following times:
• When signed output value is between
FFFF FFFF and 8000 0000 hex.
This flag can be
used as a direction
signal.
A272 00 to 15 Lower 4 digits of the
present value of the
internal pulse output
(absolute value for
absolute coordi-
nates)
8000 0000 to 7FFF
FFFF hex
(
−
2,147,483,648 to
2,147,483,647)
Contains absolute movement value
when pulses are output to error
counter.
Cleared to zero at following times:
• When power to CPU Unit is turned ON
• When operation is started
Updated at following times:
• Cyclically on error counter cycle
This value can be
used to monitor the
present value of
the internal pulse
output as an abso-
lute value when
using absolute
coordinates.
A273 00 to 15 Upper 4 digits of the
present value of the
internal pulse output
(absolute value for
absolute coordi-
nates)
Word
Bits
Function
Data range
Refresh timing
Application
examples
Word
Bits
Function
Data range
Refresh timing
Application
examples
A32
00 to 15 Error counter 0
present value
(signed)
8000 to 7FFF hex
(
−
32,768 to
32,767)
Cleared to zero at following times:
• When power to CPU Unit is turned ON
• At start of operation
• When an error counter error occurs
Updated at following times:
• Cyclically according to error counter
cycle
Saved at following times:
• When Error Counter Disable Bit
(A562.01) is turned ON.
Use to monitor the
difference between
the target value
and the present
value.
A38
00 to 15 Lower 4 digits of
present value of
pulse output to
inverter (relative
value)
8000 0000 to 7FFF
FFFF hex
(
−
2,147,483,648 to
2,147,483,647)
Contains relative internal pulse output
value when pulses are output to error
counter.
Cleared to zero at following times:
• When power to CPU Unit is turned ON
• When operation is started
• When pulse output to error counter is
started
Updated at following times:
• Cyclically on error counter cycle
These values can
be used to monitor
the present value
of internal pulse
output.
A39
00 to 15 Upper 4 digits of
present value of
pulse output to
inverter (relative
value)
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...