CompoBus/S I/O Link Units
Section 7-6
Description of Operation
7-6
CompoBus/S I/O Link Units
The CP1L can function as a slave to a CompoBus/S Master Unit (or SRM1
CompoBus/S Master Control Unit) when a CP1W-SRT21/CPM1A-SRT21
CompoBus/S I/O Link Unit is connected. The CompoBus/S I/O Link Unit
establishes an I/O link of 8 inputs and 8 outputs between the Master Unit and
the PLC. Up to three CompoBus/S I/O Link Units, including other Expansion I/
O Units, can be connected to a CP1L CPU Unit.
From the standpoint of the CP1L CPU Unit, the 8 input bits and 8 output bits
allocated to the CompoBus/S I/O Link Unit are identical to input and output
bits allocated to Expansion I/O Units even though the CompoBus/S I/O Link
Unit does not control actual inputs and outputs. The input and output bits allo-
cated to the CompoBus/S I/O Link Unit are one side of an I/O link between the
slave CPU Unit and the CPU Unit to which the Master Unit is connected.
CIO 2000
CIO 2002
CIO 2: Leftmost 3 digits of temperature data
0 16
5
16
4
16
3
0 0 16
5
16
4
CIO 2001 16
4
16
3
16
1
16
0
0 16
5
16
4
16
3
CIO 2: Rightmost 3 digits of temperature data
1 16
2
16
1
16
1
(2)
(1)
(9) If temperature data is negative, "8" is written here.
(3)
D101
0/8 10
6
10
5
10
4
D103
0 1 0 0
#0100
CIO 2002
−
2's complement data
D100
10
3
10
2
10
1
10
0
H1
0 0 16
5
16
4
H0
16
3
16
2
16
1
16
0
(5)
(4)
(1)
D102
0 0 0 0
#0000
CIO 2001
2's complement data
(6)
If the temperature data is
non-negative, binary data is
converted to BCD data.
(8)
If the temperature data is negative,
binary data is converted to BCD data.
(7)
Binary
subtraction
BD L NC( BS-) N C
BD H
NC( BS+)
S
COMM
ERR
ON
1 2
3
4 5
6
No.
SRT21
EXP
SYSMAC
CP1L
L1
L2/N
COM
01
03
05
07
09
11
01
03
05
07
09
11
00
02
04
06
08
10
00
02
04
06
08
10
00
01
02
03
04
06
00
01
03
04
06
COM
COM
COM
COM
05
07
COM
02
COM
05
07
IN
OUT
CP1L CPU Unit
Special flat cable or VCTF cable
CompoBus/S Master Unit
(or SRM1 CompoBus/S
Master Control Unit)
CP1W-SRT21/
CPM1A-SRT21
CompoBus/S
I/O Link Unit
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...