![background image](http://html1.mh-extra.com/html/omron/cp1l-12-2007/cp1l-12-2007_operation-manual_742083589.webp)
554
Auxiliary Area Allocations by Address
Appendix D
A400
All
Error code
When a non-fatal error (user-defined
FALS(006) or system error) or a fatal
error (user-defined FALS(007) or
system error) occurs, the 4-digit
hexadecimal error code is written to
this word. When two or more errors
occur simultaneously, the highest
error code will be recorded.
---
Cleared
Cleared
Refreshed
when error
occurs.
---
A401
A401.00 Other Fatal
Error Flag
ON when a fatal error that is not
defined for A401.01 to A401.15
occurs. Detailed information is output
to the bits of A314.
There are no errors that affect this
flag at this time. This flag is reserved
by the system.
OFF: No
other fatal
error
ON: Other
fatal error
Cleared
Cleared
Refreshed
when error
occurs.
A314
A401.06 FALS Error
Flag
(fatal error)
ON when a fatal error is generated
by the FALS(006) instruction. The
CPU Unit will stop operating and the
ERR/ALM indicator will light.
The corresponding error code will be
written to A400. Error codes C101 to
C2FF correspond to FALS numbers
001 to 511.
This flag will be turned OFF when
the FALS errors are cleared.
ON:
FALS(006)
executed
OFF:
FALS(006)
not executed
Cleared
Cleared
Refreshed
when error
occurs.
A400
A401.08 Cycle Time
Too Long Flag
(fatal error)
ON if the cycle time exceeds the
maximum cycle time set in the PLC
Setup (the cycle time monitoring
time). CPU Unit operation will stop
and the ERR/ALM indicator on the
front of the CPU Unit will light.
This flag will be turned OFF when
the error is cleared.
OFF: Cycle
time under
max.
ON: Cycle
time over
max.
Cleared
Cleared
Refreshed
when the
cycle time
exceeds
maximum.
PLC
Setup
(Cycle
time moni-
toring
time)
A401.09 Program Error
Flag
(fatal error)
ON when program contents are
incorrect.
CPU Unit operation will stop and the
ERR/ALM indicator on the front of
the CPU Unit will light. The task num-
ber where the error occurred will be
stored in A294 and the program
address will be stored in A298 and
A299.
The type of program error that
occurred will be stored in A295.08 to
A295.15. Refer to the description of
A295 for more details on program
errors.
This flag will be turned OFF when
the error is cleared.
ON: Error
OFF: No error
Cleared
Cleared
Refreshed
when error
occurs.
A294,
A295,
A298 and
A299
Address
Name
Function
Settings
Status
after
mode
change
Status
at star-
tup
Write
timing
Related
flags, set-
tings
Words
Bits
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...